Installation and Programming Manual
Mircom Technologies Inc
All Rights Reserved
LT-1034 Rev.1
Page 28 of 54
5.5 Changing the Pass Codes
To change the pass codes, you must be logged into, or above, the level you are changing. Select:
[
ADMINISTRATION
]
[
CHANGE PASSCODE
].
Select the access level to change then enter new pass code
5.6 Displaying the NMC Firmware version
At Access Level 1
Select [
DISPLAY
VERSION
]
The NMC Version, the IC (PB) Version and the Model Version will be displayed.
There are three (3) Model Versions of firmware:
1. US UL985 (200 sec trouble delay,
NO
10 min silencing timer, 5 min silence inhibit, 10 min auto alarm silence
timer)
2. Canadian ULC527 (90 sec trouble delay)
3. Demo (15 sec trouble delay,
NO
missing NMC battery reporting,
NO
ground fault reporting)
Demo units should not be sold. A Firmware change by the Factory will have to be performed first!
NMC VER: 01.06.05
PBVER: 3.2.15
MODEL: CANADIAN
BCK
SET DATE/TIME
VIEW LOGS
CHANGE USER ID
UP DWN ENT BCK
>CHANGE PASS CODE
UP DWN ENT BCK
DISPLAY VERSION
>ADMINISTRATION
TESTS
UP DWN ENT BCK
>DISPLAY VERSION
ADMINISTRATION
TESTS
UP DWN ENT BCK
ENT NEW PASS CODE
>
UP DWN EN T BCK
>CHG LEVEL 1 PW
CHG LEVEL 2 PW
CHG LEVEL 3 PW
UP DWN ENT BCK