Installation and Programming Manual
Mircom Technologies Inc
All Rights Reserved
LT-1034 Rev.1
Page 7 of 54
Listed to ULC S527 and ULC S545: ISD-1000-MBW, ISD-1000-MBR
•
M = Mircom.
•
B = Bilingual (English/French) label which are silenceable (Canada).
•
W = White, R = Red.
NMC-100 Information: NMC-100-MW where:
M = Mircom.
W = White, R = Red.
Power Requirements:
NMC-100 ISD-1000 PPC-600
VOLTS
120VAC 120VAC 120/240VAC
AMPS
2.0 .5 .1
Hz
60 60 60
WATTS
240 60 24
Operating Temperature:
0
o
C to 35
o
C, 32
o
F to 95
o
F
Operating Humidity:
0 to 80% Non-Condensing
Alarm Contact Rating: 5A 125VAC
Trouble Contact Rating: 5A 125VAC
1.7 Relevant Codes and Standards
The NMC-100 Network Monitoring Controller is designed to meet the requirements of:
•
NFPA 72, 1999 edition
.
•
ULC-S527-99
- Standard for Control Units for Fire Alarm Systems (Accessory).
•
ULC-S545-M86
- Standard for Residential Fire Warning System.
•
UL985
- Household Fire Warning System Units.
The ISD-1000 In-suite Signaling Devices are considered ‘modules’ of the NMC-100 Control Unit of the ‘Fire-Link’
system.
The PPC-600 Passive Phase Coupler is designed to meet
UL508 and CSA C22.2 No.14-M94
1.8 General Installation Requirements
When installing the NMC-100 control panel, the ISD-1000 In-suite Signaling Devices and the PPC-600 Passive
Phase Coupler refer to this manual. When installing optional system components and compatible alarm initiating
devices refer to the installation documents provided with those products.
1.9 Field Wiring
Field wiring recommendations in this document are intended as guidelines. All Field wiring must be installed in
accordance with NFPA 70 National Electrical Code; and in Canada, the standard for installation ULC-S524, the
most current Canadian Electrical Code, the National Building Code, the Provincial Fire Code and the Authority
Having Jurisdiction (AHJ).
1.10 Compatible Devices
Use only UL and/or ULC Listed smoke detectors that are compatible with the NMC-100 Network Monitoring
Controller as referenced in this manual.