background image

Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113

© 

Mircom 2002

Printed in Canada
Subject to change without prior notice

www.mircom.com

FA-200

Microprocessor-Based Fire Alarm Control Panel

LT-636 Rev. 13
July 2006

Installation and Operation Manual

Advanced Life Safety Solutions

Advanced Life Safety Solutions

A.C. ON

COMMON

SUPERVISORY

COMMON

TROUBLE

COMMON

ALARM

BATTERY
TROUBLE

GROUND

FAULT

REMOTE

TROUBLE

TEST

AUXILIARY

DISCONNECT

FIRE

DRILL

ZONE 1

ZONE 2

ZONE 3

ZONE 4

SIGNAL

SILENCE

SERIES 200

FIRE ALARM CONTROL

U.S.A.
60 Industrial Parkway
Cheektowaga, NY 14227
Tel: 1-888-660-4655 Fax: 1-888-660-4113

Summary of Contents for FA-200 Series

Page 1: ...LT 636 Rev 13 July 2006 Installation and Operation Manual Advanced Life Safety Solutions Advanced Life Safety Solutions A C ON COMMON SUPERVISORY COMMON TROUBLE COMMON ALARM BATTERY TROUBLE GROUND FA...

Page 2: ......

Page 3: ...minal Connections 16 DACT Dialler Module DACT 100A Terminal Connections 17 Polarity Reversal and City Tie Module Model PR 100 Terminal Connections 18 Power Supply Connections 19 Wiring Tables 20 Syste...

Page 4: ...anel 38 FA 202 Fire Alarm Control Panel 38 FA 204 Fire Alarm Control Panel 39 Polarity Reversal and City Tie Module PR 100 39 RM 204 RM 208 Relay Module 39 FA 204E Fire Alarm Control Panel 39 DM 204 Z...

Page 5: ...derations 12 Figure 11A Main Fire Alarm Module Terminal Connections 13 Figure 11B Main Fire Alarm Module Terminal Connections cont d 14 Figure 12 DM 204 Zone Adder Module Terminal Connections 15 Figur...

Page 6: ...List of Figures and Tables iv...

Page 7: ...Class B FA 204 or fa 204e Initiating Circuit three may be a Waterflow Zone as may Initiating Circuit 7 if a DM 204 is installed and initiating circuit four may be a latched or non latched supervisory...

Page 8: ...erm circuit is used Wiring Styles Initiating circuits are configured by default as Class B Style B They may be globally all or none configured as Class A Style D as described in System Configuration o...

Page 9: ...total with individual trouble indicators Common Alarm Trouble Relays Interface for Remote Trouble Indicator and or 1 to 3 of RAM 208 Remote Multiplex Annunciators Resettable Four Wire Smoke Detector P...

Page 10: ...up to 1 7 amperes each 5 amperes total RM 208 Relay Adder Module for the FA 204 or FA 204E Adds eight configurable Form C Relays rated 1A 28 VDC RM 204 Relay Adder Module for the FA 204 or FA 204E Add...

Page 11: ...FA 202 or FA 204 Figure 1 FA 201 202 and 204 Enclosure Installation and Dimensions DOOR BACKBOX WALL SIDE VIEW SURFACE DOOR 8 3 3 BACKBOX DIA WALL SIDE VIEW FLUSH BACKBOX DOOR 16 5 13 4 3 5 8 1 1 2 1...

Page 12: ...H PAINTED DOOR 16GA 0 059 THICK COLD ROLLED STEEL DOOR BACKBOX SIDE VIEW SURFACE DOOR 4 5 1 BACKBOX SIDE VIEW FLUSH BACKBOX DOOR 16 5 WALL WALL 32 7 DIA HOLE 7 8 15 16 5 16 14 3 11 1 2 14 1 5 4 3 1 2...

Page 13: ...below Be sure to connect a solid Earth Ground from building system ground to a cold water pipe to the Chassis Earth Ground Mounting Lug and to connect the Earth Ground Wire Lugs from the Main Chassis...

Page 14: ...4 or RM 208 2 Only one of PR 100 or DACT 100A may be installed P8 P7 SEE NOTE 2 MODEL DACT 100A DIALER MODULE SEE NOTE 2 MODEL PR 100 POLARITY REVERSAL AND CITY TIE MODULE M F HEX SPACER 6 32 x 7 8 SC...

Page 15: ...ity Tie is installed The City Tie is plugged into P8 Battery Connected to P2 P3 via the factory installed cables Transformer Factory wired to P4 P5 do not disconnect JW5 There should be no jumper here...

Page 16: ...h JW1A Alarm or supervisory control for Relay 1 JW2A Alarm or supervisory control for Relay 2 JW8A Alarm or supervisory control for Relay 8 Finally there are jumpers JW1 2 JW2 3 up to JW7 8 that allow...

Page 17: ...is jumper is cut and a system trouble occur the designated terminals will transmit a zero volts or open circuit Please note that at normal condition the terminals polarity is read exactly as labelled...

Page 18: ...t to properly dress the wires so as not to place stress on either their connection to the boards or running to conduit The Figure below shows the required wiring techniques Figure 10 General Field Wir...

Page 19: ...relay contacts will act as a second set of common alarm contacts if there are no initiating circuits set as supervisory Initiating circuits must be all either Style B or D If Style D is selected cut t...

Page 20: ...3 9K 1 2W ELR LISTED S5434 MODEL MP 300 MANUFACTURED BY MIRCOM PULL STATION S RS 485 1 TO 3 OF RAM 208 REMOTE ANNUNCIATORS SEE RAM 208 OPERATION INSTALLATION MANUAL NOT USED WITH RTI 24VDC POWER POWE...

Page 21: ...SWITCH NO HEAT DETECTOR LEGEND See Appendix A for compatible devices SMOKE DETECTOR 3 9K 1 2W ELR LISTED S5434 MODEL MP 300 MANUFACTURED BY MIRCOM PULL STATION CLASS A STYLE D NOTE INITIATING CIRCUIT...

Page 22: ...ed source of supply NO NC RELAY 2 COM NO NC RELAY 1 COM NO NC RELAY 3 COM NO NC RELAY 4 COM NO NC RELAY 5 COM NO NC RELAY 6 COM NO NC RELAY 7 COM NO NC RELAY 8 COM RELAY CONTACTS 28 VDC 1 AMP RESISTIV...

Page 23: ...Line 3 Output Tip Ring To an optional Premise Telephone on the second Telephone Line via the required RJ31X Connector Note that most AHJs do not allow the connection of premise telephones See Wiring...

Page 24: ...e alarm module Cut Jumper JW on the PR 100 module in order to transmit a trouble condition to the monitoring station All circuits are power limited and must use type FPL FPLR or FPLP power limited cab...

Page 25: ...e FA 201 FA 202 FA 204 120 V 60Hz 2A 240V 50 Hz 1A 2 75 A maximum F1 Replace with 10 amp 1 1 4 fast acting fuse FA 204E 120 V 60Hz 2A 240V 50 Hz 1A 6 A maximum F1 Replace with 10 Amp 1 1 4 Fast Acting...

Page 26: ...Maximum Wiring Run to Last Device ELR AWG ft m 22 2990 910 20 4760 1450 18 7560 2300 16 12000 3600 14 19000 5800 12 30400 9200 Note Maximum loop resistance should not exceed 100 Ohms Total Signal Loa...

Page 27: ...tly and the Common Trouble LED should flash 3 Connect the batteries while observing correct polarity the red wire is positive and black wire is negative All indicators should extinguish except for nor...

Page 28: ...AC power is within acceptable levels It turns off when the level falls below the power fail threshold and the panel switches to standby battery power Common Alarm LED The Common Alarm indicator turns...

Page 29: ...at common alarm and common supervisory relays and any RM 204 RM 208 relays are not activated The trouble relay is activated If installed dialler or polarity reversal and city tie modules are also inac...

Page 30: ...and common supervisory relays and any RM 204 RM 208 relays are not activated The trouble relay is activated If installed dialler or polarity reversal and city tie modules are also inactive causing a...

Page 31: ...ed that aux disconnect is not active Signals and strobes are activated Subsequent Alarms when the panel is already in alarm cause the following The buzzer sounds steadily If signals have been silenced...

Page 32: ...rm for water flow sensors These alarms are identical to normal non verified alarms except that any indicating circuits programmed to these circuits all are by default are non silenceable Also if water...

Page 33: ...such as bells and piezo mini horns that may not be silenced either manually or automatically While sounding these follow the pattern appropriate for the condition the configured evacuation code defaul...

Page 34: ...Switch Settings on the Main Fire Alarm Board For DIP Switches 0 switch off 1 Switch on The DIP switches are located on the bottom left side of the main fire alarm board MAIN FIRE ALARM BOARD FIELD WI...

Page 35: ...terflow Switch 11 4 Alarm Waterflow Initiating Circuit 4 Alarm or Supervisory Switch 11 5 Normal Verified Alarm no effect on Supv Switch 11 6 Alarm Supervisory Switch 11 7 Non Latching Supervisory No...

Page 36: ...A B Style Z Y indicating circuits is only a matter of how they are wired See connection information on page 13 If Class A Style D initiating circuits are selected FA 202 FA 204 FA 204E only the appro...

Page 37: ...e to create Class A Circuit 4 DIP switches for circuits 5 to 8 are ignored and led indicators for circuits 5 to 8 are non functional Function DIP Switch on DM 204 Module Switch Off Switch On Indicatin...

Page 38: ...f Initiating Circuit 3 is first activated the indication circuits will sound for three bursts Any subsequent activations of Initiating Circuit 3 will sound for one burst The initial burst interval den...

Page 39: ...2 SIJ 24 NS6 220 6269C 003 PSD 7130 70 201000 003 SIJ 24 NS4 220 6270C 003 PSD 7130 70 201000 005 SIJ 24 HSC 220R PSD 7128 70 201000 001 SLR 24 NS6 220 Cerebrus Pyrotronics PSD 7126 70 201000 002 SLR...

Page 40: ...DCD 135 HSC 220R HD 3 HB 3 0 035mA 2451 B406B A A 0 12 mA DCD 190 NS6 220 HD 3 HB 3 0 035mA 2451 DH400 A N A 0 12 mA DCD 190 NS4 220 HD 3 HB 3 0 035mA 2451TH B406B A A 0 12 mA DCD 190 HSC 220R HD 3 HB...

Page 41: ...U S10A S00 0 10 mA 1451 B401B A A 0 12 mA 731U 702E 702U 702RE 702RU S11A S00 0 10 mA 1451 B406B A A 0 12 mA 732U 702E 702U 702RE 702RU S11A S00 0 10 mA 1451DH DH400 A A 0 12 mA Detection Systems Inc...

Page 42: ...AS 2475W FR AS 24110W FR AS 2415C FW AS 2430C FW AS 2475C FW AS 24100C FW AH 24 R AH 24 WP R NS 2415W FR NS 241575W FR NS 2430W FR NS 2475W FR NS 24110W FR NS4 2415W FR NS4 241575W FR NS4 2430W FR NS4...

Page 43: ...ndix B RAM 208 Remote Annunciator The RAM 208 Eight Zone Remote Annunciator mounts in an electrical box It provides annunciation for the FA 204 or FA 204E s full complement of 8 Initiating circuits Fo...

Page 44: ...supply Power limited 24VDC 300mA max unfiltered for RTI or remote annunciators 1 RTI Interface for connection to an RTI Remote Trouble Indicator Auxiliary relays resistive loads Common Alarm Form C 1A...

Page 45: ...A 8 mA max shorted Current consumption standby 35 mA alarm 300 mA RM 204 RM 208 Relay Module Four or eight relays Form C 1A resistive 28 VDC per contacts Each individual relay can be relay per zone co...

Page 46: ...mA max alarm Two Class B or A Style Y or Z indicating circuits configurable as strobes or audibles Power limited 24 VDC unfiltered 1 7A 49 C per Circuit Current consumption standby 45 mA alarm 120 mA...

Page 47: ...eries Use BA 110 10AH Batteries for the FA 204E The FA 204E will charge up to 24AH batteries if they are in an external Mircom BC 160 Battery Cabinet IMPORTANT NOTICE The main AC branch circuit connec...

Page 48: ...tandby 60 hrs standby 5 min alarm FA 201 2 4 Basic4 AH batteries 4 AH batteries not possible FA 201 2 4 DACT 100A RM 208 RTI 6 5 AH batteries not possible FA 204E DM 204 10 AH batteries 12 AH batterie...

Page 49: ...will be prepaid by Mircom We shall not be responsible to repair or replace equipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged in any way U...

Page 50: ......

Page 51: ......

Page 52: ...5W3 Tel 905 660 4655 Fax 905 660 4113 Mircom 2005 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway Cheektowaga NY 142...

Reviews: