FA-200 Series Installation and Operation Manual
39
FA-204 Fire Alarm Control Panel
Same as FA-201, plus ...
• Four supervised Class B (Style B) or two Class A ( Style D) Initiating circuits; configurable (normal or verified,
and for Class B there may be one waterflow and one supervisory). [Compatibility ID “A”]
• Optional RM-204 or RM-208 Relay Module.
• One RS-485 connection for up to 3 RAM-208 Remote Annunciators.
• Auxiliary relays:
(resistive loads) common alarm, supervisory, trouble
all are Form C, 1 amp, 28VDC
• DACT / Dialler Module (DACT-100A)
• DACT - “Digital Alarm Communicator Transmitter”
• Using Ademco Contact ID and SIA-DCS Protocols.
• See Mircom document LT-617 for further info.
• Current Consumption:
standby:
45 mA
alarm:
120 mA
Polarity Reversal and City Tie Module (PR-100)
• Supervised city tie:
not power limited
• 24VDC unfiltered, 210 mA max., Trip coil: 14 ohms
• Polarity reversal:
power limited
• 24VDC open, 12VDC @ 3.5 mA, 8 mA max. (shorted)
• Current consumption:
standby:
35 mA
alarm:
300 mA
RM-204 / RM-208 Relay Module
• Four or eight relays:
Form C, 1A (resistive), 28 VDC per contacts
• Each individual relay can be relay per zone, common alarm, common supervisory
• Current Consumption:
standby:
5 mA
alarm:
160 mA
FA-204E Fire Alarm Control Panel
General
• Four supervised Style B (Class B) or 2 Style D (Class A) initiating circuits; configurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
• Two Class A/B (Style Y/ Z) indicating circuits; configurable as strobes or audibles.
Power limited:24 VDC unfiltered
• 1.7 A @ 49°C per circuit (5A total)
• One DM-204 Zone Adder Module may be added.
• Initiating circuit disconnect switches.
• Optional DACT or city tie adder module.
• Optional RM-204 / RM-208 Relay Module.
• Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple
• Aux power supply.
• Power limited: 24VDC, 300mA max, unfiltered
• for RTI or Remote Annunciators
• 1 RS-485 connection for up to 3 RAM-208 Remote Annunciators.
• 1 RTI interface for connection to an RTI Remote Trouble Indicator.