System Configuration
30
When configuring the FA-200 main board, keep in mind the following information:
• Only indicating circuit two may be configured for visual devices.
• If initiating circuit three is configured as waterflow, the corresponding verified selection becomes a retard
selection.
• If initiating circuit four is configured as alarm, the corresponding latching selection has no effect.
• If initiating circuit four is configured as supervisory, the corresponding verified selection has no effect.
• The selection of Class A/B (Style Z/Y) indicating circuits is only a matter of how they are wired. See connection
information on page 13 .
• If Class A (Style D) initiating circuits are selected (FA-202, FA-204, FA-204E only), the appropriate board
jumpers must also be set. Class B initiating circuits one and two combine to create Class A Circuit #1, and Class
B initiating circuits three and four combine to create Class A Circuit #2. DIP switches for circuits three and four
are ignored except for an FA-204E with a DM-204 Adder Module. LED indicators for circuits three and four are
non-functional except for an FA-204E with a DM-204 Adder Module.
DM-204 Module
On the DM-204 Zone Adder Module the DIP switches are located on the bottom right-hand corner.