FA-200 Series Installation and Operation Manual
13
Main Fire Alarm Module Terminal Connections
Wire devices to terminals as shown in
Figure 11
below. See
Wiring Tables
on page 20 for wiring instructions,
Appendix A
on page 33 for compatible devices, and
Appendix C
on page 38 for specifications.
Figure 11A: Main Fire Alarm Module Terminal Connections
When wiring devices, please keep in mind the following:
• All terminals are shown from the back of the main fire alarm board assembly (pointing towards the rear of the
enclosure).
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 1.5 vp-p ripple, 50 mA max. alarm.
They may be configured as required. The alarm threshold is 21 mA. Maximum loop resistance is 100 ohms, 50
ohms per side.
• Indicating circuits are fully supervised and rated for 24 VDC unfiltered 1.7 amp max. each They must be wired
as shown in the wiring tables on page 20.
• On the FA-204 & FA-204E, the auxiliary common supervisory relay contacts will act as a second set of common
alarm contacts if there are no initiating circuits set as supervisory.
• Initiating circuits must be all either Style B or D. If Style D is selected, cut the number of circuits in half.
ATTENTION:
Do not exceed power supply ratings:
•FA-201, FA-202, FA-204, total current for indicating circuits is 2.4 A max.
•FA-204E, total current for indicating circuits is 5 A max.
AUX. POWER NEGATIVE FOR
REMOTE ANNUNCIATORS
NO
NC
COM
TROUBLE
RELAY
NO
NC
COM
SUPV.
RELAY
NO
NC
ALARM
RELAY
MUST BE
CONNECTED TO A
LISTED POWER
LIMITED SOURCE
OF SUPPLY
COMMON TROUBLE
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
AUXILIARY COMMON
SUPERVISORY
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
(NOT PRESENT ON
FA- 201 & FA-202)
AUXILIARY COMMON
ALARM CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
(POWER LIMITED)
IND1+ (Z)
CLASS A /
STYLE Z
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
EXAMPLES OF BOTH CLASS AA@ AND AB@ WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
SUPERVISED INDICATING CIRCUIT #1
(POWER LIMITED)
BELL, HORN, OR STROBE
Legend: See Appendix A for compatible devices.
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
COM
COM-
CLASS B /
STYLE Y
WIRING