6
7
1. The DC Circuit Breaker connects and disconnects the DC bus voltage
from the Battery Pack to the UPS. The DC Circuit Breaker will trip in the
event of a DC overcurrent condition.
2. The top External Battery connector is for connecting to the UPS and/or for
Daisy Chaining additional Battery Packs.
3. The bottom External Battery connector is for Daisy Chaining additional
Battery Packs and/or connecting an external battery charger.
INSTALLATION PLACEMENT
This Battery Pack series is
ONLY
intended to be installed in an indoor tem-
perature controlled environment that is free of conductive contaminants. DO
NOT operate the Battery Pack in: extremely dusty and/or unclean areas, loca-
tions near heating devices, water or excessive humidity, or where the Battery
Pack is exposed to direct sunlight. Select a location, which will provide good
air circulation for the Battery Pack at all times.
Route cables so they cannot
be walked on or damaged. This Battery Pack series is not for use in a com-
puter room as defined in the Standard for the Protection of Electronic Com-
puter/Data Processing Equipment ANSI/NFPA 75. Typical battery life is 3 to 5
years. Environmental factors do affect battery life. High temperatures, poor
ventilations and frequent, short duration discharges have a negative impact on
battery life.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the Battery Pack. Place the Battery Pack in the final desired location and
complete the rest of the installation procedure.
WARNING!
These Battery Packs are extremely heavy. Any time the Battery
Pack has to be handled be sure to use, enough personnel, strong supports
and equipment to safely handle the Battery Pack.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE BAT-
TERY PACK.
The mounting brackets are
ONLY
for securing the Battery Pack
to the rack.
Chapter 2: Rear Panels
Chapter 3: Installation
NOTE:
If you are using more than one of these Battery Packs with the
Endeavor 5-10KVA RT series UPS, the UPS must be configured so that the
UPS will report the correct estimated runtime on the LCD screen and in the
Power Monitoring software and/or the SNMP card. See the Power Monitoring
software or the SNMP card’s User's Manual to configure the UPS.
Operating Temperature (Maximum): 0 to 40
°
C (+32 to +104
°
F)
Operating Elevation: 0 to 2,000m (0 to +6,562 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +50°C (+5 to +122°F)
Storage Elevation: 0 to 15,000m (0 to +49,213 ft)