31. Reconnect all of the battery cables.
32. Turn on all of the DC circuit breakers on the rear panel of all of the Battery

Packs.

33. Properly dispose of the old batteries at an appropriate recycling facility or

return them to the supplier in the packing material for the new batteries.

34. The Battery Pack is ready for normal operation.

NOTE:

  If the UPS has a Weak/Bad Battery Alarm after replacing the batter-

ies, the user must initiate a self-test to clear the Weak/Bad Battery Alarm.  To
initiate a self-test see section 4 "

ON / OFF/ TEST BUTTON

" in the UPS's

User's Manual.

BP192RTXL

(QUALIFIED

 

SERVICE PERSONNEL ONLY)

1.

Turn off the equipment that is plugged into the output receptacles of the
UPS.

2.

Press and release the On/Off/Test button on the front panel to turn the
UPS off.

3.

Disconnect the UPS from the utility power.

4.

Unplug the equipment from the output receptacles of the UPS.

5.

Unplug the computer interface cable from the rear panel of the UPS.

6.

Turn off all of the DC circuit breakers on the rear panel of all of the Battery
Packs.

7.

Disconnect all of the battery cables.

8.

Remove the Battery Pack from the rack and lay on the floor or a tabletop.

USE CAUTION:

  These Battery Packs are extremely heavy.  Use two or more

people when removing the Battery Pack.
9.

Remove the front panel retaining screws.

10. Remove the front panel and set aside.
11. Remove the cover screws from the top cover.
12. Remove the cover and set aside.
13. Remove the retaining screws for the battery retaining bracket.
14. Remove the battery retaining bracket and set aside.

NOTE: 

 Before disconnecting the battery wires it is recommended that you

draw a diagram of how the batteries are connected.
15. On the right hand side at the rear find the Anderson connector holder box.

Open the box and disconnect the battery positive (red) and battery nega-
tive (black) Anderson connectors.

16. On the left hand side in the middle find the Anderson connector holder

box.  Open the box and disconnect the Anderson connectors.

USE CAUTION:  

The battery modules are heavy.

17. Slide the front battery module out and set on a tabletop.
18. Slide the rear battery module out and set on a tabletop.
19. Open the battery modules one at a time.
20. Disconnect all of the battery wires.
21. Remove all of the defective batteries and set aside.
22. Install the new batteries in the same orientation as the original batteries.
23. Verify proper polarity.  Re-install the battery wires.
24. Re-install the battery modules.
25. Reconnect the Anderson connector on the left hand side.  Re-install the

Anderson connector holder box.

26. Reconnect the Anderson connectors on the right hand side.  Re-install the

Anderson connector holder box.

27. Re-install the battery retaining bracket and secure with the retaining screws.
28. Re-install the top cover and secure with the retaining screws
29. Re-install the front panel and secure with the retaining screws.
30. Re-install the Battery Pack in the rack.

Summary of Contents for BP192RTXL

Page 1: ...a Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com P N 34000472 R2 User s Manual BP192RTXL BP240RTXL Battery Pac...

Page 2: ...1 1 Introduction 2 2 Rear Panels 6 3 Installation 7 4 Operation 12 5 Replacing the Battery 12 6 Obtaining Service 18 7 Specifications 19 8 Limited Product Warranty 20 Table Of Contents...

Page 3: ...O LIFT THE BAT TERY PACK The mounting brackets are ONLY for securing the Battery Pack to the rack Chapter 1 Introduction CAUTION The maximum ambient operating temperature for this Battery Pack series...

Page 4: ...hority to operate the equipment LIFE SUPPORT POLICY As a general policy we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can...

Page 5: ...Environmental factors do affect battery life High temperatures poor ventilations and frequent short duration discharges have a negative impact on battery life INSTALLATION Be sure to read the installa...

Page 6: ...location of the Battery Pack has been determined place the to wer stands in the desired location WARNING The Battery Pack must be installed in the proper up right posi tion Once the Battery Pack is p...

Page 7: ...the UPS NOTE There is no maximum number for Daisy Chaining the Battery Packs however the recharge time will increase exponentially for every Battery Pack added 1 The UPS MUST be in the off position 2...

Page 8: ...rly The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly Refer to local codes for proper disposal requirements or return the battery to the supp...

Page 9: ...1 Remove the retaining screws for the battery retaining brackets 12 Remove the battery retaining brackets and set aside NOTE Before disconnecting the battery wires it is recommended that you draw a di...

Page 10: ...e the cover screws from the top cover 12 Remove the cover and set aside 13 Remove the retaining screws for the battery retaining bracket 14 Remove the battery retaining bracket and set aside NOTE Befo...

Page 11: ...on the failure including LEDs that may be illuminated or error codes displayed f A description of the protected equipment including model numbers if possible g A technician will ask you for the above...

Page 12: ...ructions Any technical advice furnished before or after delivery in regard to use or application of Para Systems equipment is furnished without charge and on the basis that it represents Para Systems...