18
19
Battery Type
Typical Recharge Time
Battery Part Number
Model Number
SYSTEM SPECIFICATIONS
Format
Rack/Tower Convertible
DC Current
39.2 Amps
BATTERY SYSTEM
Typical Battery Life
Battery Quantity
System Voltage
Sealed, Non-Spillable, Maintenance Free, Value Regulated, Lead Acid
3-5 years, depending on discharge cycles and ambient temp
Battery Cable Length
21" / 533.4mm
PHYSICAL
Weight - Net
Size - Net
L X W X H
Size - Shipping
L X W X H
Weight - Shipping
23.4 x 17.3 x 5.14"
595 x 440 x 130.6 mm
29.5 x 23.6 x 10.9"
750 x 600 x 276 mm
REGULATORY COMPLIANCE
Safety and Approvals
EMC Verification
cTUVus (Conforms to UL1778 4th Edition & CSA 22.2 no. 107.3-05)
FCC Class B, CE certified
B00056
B00058
122.4 lbs
55.5 Kgs
80.5 lbs
36.5 Kgs
134.5 lbs
61.0 Kgs
172.0 lbs
78.0 Kgs
16
20
192VDC
240VDC
BP192RTXL
BP240RTXL
8-hours to 90% after full load discharge
IF THE BATTERY PACK REQUIRES SERVICE
Chapter 6: Obtaining Service
Chapter 7: Specifications
1. Verify there are no tripped circuit breakers and that the batteries are good.
A tripped circuit breaker and defective batteries are the most common iss-
ues.
2. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the issue call or fax the Technical Support department at the
following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011
or visit our Web site at www.minutemanups.com the "Discussion Board".
Before calling the Technical Support Department have the following infor-
mation available:
a)
Contact name and address.
b)
Where and when the unit was purchased.
c)
All of the model information about your unit.
d)
The serial number of your unit.
e)
Any information on the failure, including LEDs that may be illuminated
or error codes displayed.
f)
A description of the protected equipment including model numbers, if
possible.
g)
A technician will ask you for the above information and if possible,
help solve the issue over the phone. In the event that the unit requires
factory service, the technician will issue you a Return Material Autho-
rization Number (RMA #).
h)
If the unit is under warranty, the repairs will be done at no charge. If
the unit is not under warranty there will be a charge for the repair.
3. Pack the unit in its original packaging. If the original packaging is no lon-
ger available, ask the Technical Support Technician about obtaining a new
set. It is important to pack the unit properly in order to avoid damage in
transit. Never use Styrofoam beads for a packing material.
a)
Include a letter with your name, address, day time phone number,
RMA number, a copy of your original sales receipt, and a brief desc-
ription of the problem.
4. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
5. Return the unit by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMAN UPS
1809 W. Frankford Road, Suite 150
Carrollton, TX 75007
ATTN: RMA # _______
31.5 x 23.6 x 9.1"
800 x 600 x 230 mm
25.2 x 17.3 x 3.5"
640 x 440 x 89 mm
35.7 Amps
Battery Cable Type
Premolded #8 AWG
Output Protection
Resettable Circuit Breaker
ENVIRONMENTAL
Operating Temperature (max)
Operating/Storage Humidity
Operating Elevation
0 to 40
°
C (+32 to +104
°
F)
95% Non-Condensing
0 to 2,000m (0 to +6,562 ft)
Storage Elevation
0 to 15,000m (0 to +49,213 ft)
Storage Temperature
-15 to +50°C (+5 to +122°F)
NOTE:
These Battery Packs do not have internal chargers. The typical recharge time is based on
the UPS charging the batteries.
NOTE:
Specifications are subject to change without notice.