background image

 

 

 

Minco 

Tel: 763. 571.3121 • Fax: 763. 571.0927 •  www.minco.com • Doc. #1116290(D) 

d.  Sharp Edges - An accessible edge, projection, or corner of an enclosure, opening, 
frame, guard, handle, or the like shall be smooth and well rounded, and shall not 
cause a cut-type injury during normal use of the equipment. 

 

 

REVISIONS 

REV. 

DESCRIPTION 

DATE 

ECO 

APP. 

ADDED NOTES 2-8, WAS INST 702(-), ADDED 

“SIMPLE APPARATUS” NOTES

 

6/14/93 

10344 

MWG 

Changed diagram on calibration, Modified 
spacing  

7/19/17 

 

RAA 

 

 

INST. 704(A) 

 

Control Document, System Approvals for Intrinsically Safe Transmitters 

 

The approved entity parameters specified are for Class I, Div. 
1 Groups A, B, C, and D hazardous locations. 
 
Models 

Models 

Models 

TT210, TT211 

TT176, TT216, TT676 

TT710, TT711 

TT190, TT230 

TT220, TT221, TT720 

 

 

Vmax = 35 volts 

Vmax = 35 volts 

Vmax = 35 volts 

Imax = 150 Ma 

Imax = 150 mA 

Imax = 150 mA 

Ci = 0 

Ci = 0 

Ci = 0 

Li = 0 mH 

Li = 0 mH 

Li = 0 mH

 

 

1. The selected associated apparatus 
and intrinsically safe apparatus must 
meet the following conditions for 
single channel operation: 

 

 

Voc 

  Vmax 

 

Isc 

  Imax 

 

Ca 

  Ci 

 

La 

  Li 

 

2. The selected associated apparatus 
and intrinsically safe apparatus must 
meet the following conditions for dual 
channel or multiple single channel 
operation: 

 

 

Vt 

  Vmax 

 

It 

  Imax 

 

Ca 

  Ci 

 

La 

  Li 

 

3. Voc, Vt, Isc, It, Ca and La are 
parameters of the associated apparatus 
where: 

 

  Voc,Vt  =  maximum open circuit 

voltage 

  Isc,It  =  maximum short circuit 

current 

 

Ca  =  maximum allowable connected 

capacitance 

 

La  =  maximum allowable connected 

inductance 

Summary of Contents for TT211

Page 1: ...Tel 763 571 3121 Fax 763 571 0927 www minco com Doc 1116290 D TT211 and TT711 2 Wire Temperature Transmitter Installation and Operating Instructions TT211 TT711 INTRINSICALLY SAFE NON INCENDIVE...

Page 2: ...tion Installation If installing the Temptran in a hazardous location the installer must adhere to installation requirements as set forth by the National Electrical Code NEC and any other applicable co...

Page 3: ...erature sensor or thermocouple 3 If installing in a Class I Division 2 hazardous area then the transmitters must be mounted in a vent free enclosure meeting the Electrical Utilization Enclosure Requir...

Page 4: ...parts and wiring and external cord and cable assembly strain relief shall comply with the following tests for mechanical strength a Impact Tests The equipment shall be held firmly against a rigid supp...

Page 5: ...nd D hazardous locations Models Models Models TT210 TT211 TT176 TT216 TT676 TT710 TT711 TT190 TT230 TT220 TT221 TT720 Vmax 35 volts Vmax 35 volts Vmax 35 volts Imax 150 Ma Imax 150 mA Imax 150 mA Ci 0...

Page 6: ...ion must be in accordance with the barrier manufacturers instructions ANSI ISA RP12 6 and the National Electrical Code ANSI NFPA 70 6 Control room equipment connected to the associated apparatus must...

Page 7: ...10 TT711 TT720 FOR USE IN CLASS I DIVISION 1 GROUPS A B C D HAZARDOUS LOCATIONS BARRIER BARRIER MANUFACTURER MODEL MTL 702 MANASSAS VA 706 703 361 0111 787S 788 2441 3041 3046B 4041 R STAHL 9001 01 28...

Page 8: ...TT210 TT211 TT710 OR TT711 BROWN RED BLACK ORANGE SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT176 TT190 TT216 TT230 OR TT676 SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT220 TT221 OR TT720 NON HA...

Page 9: ...least 01 ohms to the input of the transmitter If unsure or concerned about the decade box s accuracy measure the zero and span resistance setting using a known accurate ohmmeter and record decade box...

Page 10: ...warranty of merchantability or fitness for a particular purpose and of any other obligations or liability on the part of the Seller or its employees or agents Specifications Input 100 or 1000 platinum...

Page 11: ...C C Temperature Range Use one of the over 175 range codes in the MINCO Temptran sales bulletin Note A range that is available for a particular Temptran model is not automatically available for the TT2...

Reviews: