Calibration

 

 

1.

 

Connect a power supply of 24 VDC and a digital milliammeter ( 5-1/2 digit preferred ) as 
shown in the figure, or use a loop calibrator instead of the DC supply and milliammeter. 

 

NOTE:  Zero and Span resistance values are printed on the transmitter's label. 
 
2.

 

Connect a resistance decade box with a resolution of at least .01 ohms to the input of the  
transmitter.  If  unsure or concerned about the decade box's accuracy, measure the zero and 
span resistance setting, using a known-accurate ohmmeter and record decade box settings 
before connecting decade box to the transmitter. 

 
3.

 

Set decade box resistance to simulate the 4 mA temperature. 

 
4.

 

Adjust ZERO potentiometer on the transmitter until the meter reads 4 mA. 

 
5.

 

Set decade box resistance to simulate the 20 mA temperature. 

 
6.

 

Adjust SPAN potentiometer on the transmitter until the meter reads 20 mA. 

 
7.

 

Repeat steps 3 - 7 until no further adjustment is necessary. 

 

Summary of Contents for TT211

Page 1: ...Tel 763 571 3121 Fax 763 571 0927 www minco com Doc 1116290 D TT211 and TT711 2 Wire Temperature Transmitter Installation and Operating Instructions TT211 TT711 INTRINSICALLY SAFE NON INCENDIVE...

Page 2: ...tion Installation If installing the Temptran in a hazardous location the installer must adhere to installation requirements as set forth by the National Electrical Code NEC and any other applicable co...

Page 3: ...erature sensor or thermocouple 3 If installing in a Class I Division 2 hazardous area then the transmitters must be mounted in a vent free enclosure meeting the Electrical Utilization Enclosure Requir...

Page 4: ...parts and wiring and external cord and cable assembly strain relief shall comply with the following tests for mechanical strength a Impact Tests The equipment shall be held firmly against a rigid supp...

Page 5: ...nd D hazardous locations Models Models Models TT210 TT211 TT176 TT216 TT676 TT710 TT711 TT190 TT230 TT220 TT221 TT720 Vmax 35 volts Vmax 35 volts Vmax 35 volts Imax 150 Ma Imax 150 mA Imax 150 mA Ci 0...

Page 6: ...ion must be in accordance with the barrier manufacturers instructions ANSI ISA RP12 6 and the National Electrical Code ANSI NFPA 70 6 Control room equipment connected to the associated apparatus must...

Page 7: ...10 TT711 TT720 FOR USE IN CLASS I DIVISION 1 GROUPS A B C D HAZARDOUS LOCATIONS BARRIER BARRIER MANUFACTURER MODEL MTL 702 MANASSAS VA 706 703 361 0111 787S 788 2441 3041 3046B 4041 R STAHL 9001 01 28...

Page 8: ...TT210 TT211 TT710 OR TT711 BROWN RED BLACK ORANGE SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT176 TT190 TT216 TT230 OR TT676 SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT220 TT221 OR TT720 NON HA...

Page 9: ...least 01 ohms to the input of the transmitter If unsure or concerned about the decade box s accuracy measure the zero and span resistance setting using a known accurate ohmmeter and record decade box...

Page 10: ...warranty of merchantability or fitness for a particular purpose and of any other obligations or liability on the part of the Seller or its employees or agents Specifications Input 100 or 1000 platinum...

Page 11: ...C C Temperature Range Use one of the over 175 range codes in the MINCO Temptran sales bulletin Note A range that is available for a particular Temptran model is not automatically available for the TT2...

Reviews: