Wiring Diagram 

 

R1

LINE
POWER

CONTROL ROOM

RESISTANCE

4-20 mA LOOP

COPPER LEADS,
TWISTED PAIR

CONTROLLER

AND/OR

INDICATOR

DC
SUPPLY

REMOTE SENSING SITE

THERMOMETER

TEMPTRAN

 

 

Installation

 

of TT211 and TT711 Temptrans

TM

 in Class I, Division 1 or 2, Groups A, B, C, and D 

hazardous locations. 
 
Read these instructions thoroughly before installing transmitters. 
 
Per Factory Mutual, 
  1) 

Installation shall be in accord with these instructions and the National Electric Code. 

  2) 

If installing in a Class I, Division 1 hazardous area, then refer to document INST. 704, 
"CONTROL DOCUMENT, SYSTEM APPROVALS FOR INTRINSICALLY SAFE 
TRANSMITTERS" on pages 5-7 of this manual. The Simple Apparatus, referenced in 
these pages, is the RTD temperature sensor or thermocouple. 

  3) 

If installing in a Class I, Division 2 hazardous area, then the transmitters must be 
mounted in a vent-free enclosure, meeting the "Electrical Utilization Enclosure 
Requirements" stated below with which only the Approved equipment will be installed.  
All unused openings should be sealed. 

  4) 

Tampering and replacement with non-factory components may adversely affect the safe 
use of the system. 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Utilization Enclosure Requirements (Required for Division 2 areas only)

 

 
1.  Each of the transmitters must be mounted within an enclosure to prevent personal injury 
resulting from accessibility to live parts.  This enclosure must comply with the requirements 
listed below.  Further details of the enclosure requirements may be found in ANSI/ISA 
Standards S82.01, S82.02, and S82.03. 
 

1.1 Accessibility - The transmitters must be installed within the enclosure so that its 
circuits are accessible by the use of a tool only.  A part is accessible when a) the IEC 

Summary of Contents for TT211

Page 1: ...Tel 763 571 3121 Fax 763 571 0927 www minco com Doc 1116290 D TT211 and TT711 2 Wire Temperature Transmitter Installation and Operating Instructions TT211 TT711 INTRINSICALLY SAFE NON INCENDIVE...

Page 2: ...tion Installation If installing the Temptran in a hazardous location the installer must adhere to installation requirements as set forth by the National Electrical Code NEC and any other applicable co...

Page 3: ...erature sensor or thermocouple 3 If installing in a Class I Division 2 hazardous area then the transmitters must be mounted in a vent free enclosure meeting the Electrical Utilization Enclosure Requir...

Page 4: ...parts and wiring and external cord and cable assembly strain relief shall comply with the following tests for mechanical strength a Impact Tests The equipment shall be held firmly against a rigid supp...

Page 5: ...nd D hazardous locations Models Models Models TT210 TT211 TT176 TT216 TT676 TT710 TT711 TT190 TT230 TT220 TT221 TT720 Vmax 35 volts Vmax 35 volts Vmax 35 volts Imax 150 Ma Imax 150 mA Imax 150 mA Ci 0...

Page 6: ...ion must be in accordance with the barrier manufacturers instructions ANSI ISA RP12 6 and the National Electrical Code ANSI NFPA 70 6 Control room equipment connected to the associated apparatus must...

Page 7: ...10 TT711 TT720 FOR USE IN CLASS I DIVISION 1 GROUPS A B C D HAZARDOUS LOCATIONS BARRIER BARRIER MANUFACTURER MODEL MTL 702 MANASSAS VA 706 703 361 0111 787S 788 2441 3041 3046B 4041 R STAHL 9001 01 28...

Page 8: ...TT210 TT211 TT710 OR TT711 BROWN RED BLACK ORANGE SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT176 TT190 TT216 TT230 OR TT676 SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT220 TT221 OR TT720 NON HA...

Page 9: ...least 01 ohms to the input of the transmitter If unsure or concerned about the decade box s accuracy measure the zero and span resistance setting using a known accurate ohmmeter and record decade box...

Page 10: ...warranty of merchantability or fitness for a particular purpose and of any other obligations or liability on the part of the Seller or its employees or agents Specifications Input 100 or 1000 platinum...

Page 11: ...C C Temperature Range Use one of the over 175 range codes in the MINCO Temptran sales bulletin Note A range that is available for a particular Temptran model is not automatically available for the TT2...

Reviews: