Calibration
Calibration procedure
Calibrate the BOSS-1Q using the following procedure:
1.
Ensure that no power is applied to the drive.
2.
Set the ENABLE/DISABLE switch to the ENABLE
position (open), or remove the short between the
ENABLE and COM terminals on TB501.
3.
Set the RUN/BRAKE switch to the RUN position
(closed), or add a jumper between the RUN/BRAKE and
COM terminals on TB501.
4.
Set the FWD/REV switch to the desired direction.
5.
Set the MAX SPD and REGULATION trimpots to the
center of travel (12 o'clock position).
6.
Set the MIN SPD, ACCEL and DECEL trimpots full
counterclockwise (CCW).
7.
Set the TQ LIMIT trimpot full clockwise (CW).
8.
Set the signal input (analog voltage signal or speed adjust
potentiometer) to zero.
9.
Apply power to the drive.
10. Calibrate the trimpots as follows: