Page 56
MiniRanger Plus – INSTRUCTION MANUAL
7ML19981CJ02
P664 Temperature
View the temperature in °C as registered by the transducer's integral temperature sensor
(Echomax series). If a non temperature sensing transducer is being used, the fixed
temperature (P661) is displayed.
P740 Peripheral Communication
Determines the ASCII message format.
The MiniRanger Plus Rack and Panel units provide a proprietary 20 mA bipolar current
loop for communication with the Siemens Milltronics BIC-2 peripheral device.
The MiniRanger Plus uses simplex convention communication protocol. Data messages
are continuously transmitted at regular intervals (no poll is required) at 4800 baud. All
data is transmitted in structured messages of ASCII characters consisting of 8 data bits,
no parity, and 1 stop bit.
If Peripheral Communications (P740) is set for "formatted" messages, a comma is inserted
between each message field (except immediately preceding the "End of Message"
characters).
MT-00
Measurement Message
Values
Range: -50 to 150 °C
Notes
•
Not accessible via application device keypad
•
Accessible only via Dolphin.
Note:
Applicable to rack and panel units only.
Values
0
off (if communication is not required)
1
unformatted (messages are transmitted in a continuous string)
2
formatted (commas are inserted between message fields)
Field Name
Definition
Start Of Message
STX ($02)
Message Type
2 characters, 00 (indicates the following data pertains to a scan
point measurement)
Point #
3 characters, 001 (e.g. the message pertains to Point Number 1)
Reading
5 characters, 0.000 to 9999. (e.g. reading = 678.9, DDDD. = no data,
EEEE. = overflow)
Start of Message
Point #
Status A
Status C
Percent
End of Message
Temperature
Status B
Reading
Message Type
e.g.