P052 Tank Dimension 'A'
This is dimension 'A' as used in P050 Tank Shape.
Enter the height of the tank bottom if P050 = 2, 3, 4, or 5, or the length of one end section
of the tank if P050 = 7.
Enter the dimension in units (P005)
P053 Tank Dimension 'L'
This is dimension 'L' as used in P050 Tank Shape.
Enter the tank length (excluding both end sections) if P050 = 7.
Enter the dimension in units (P005)
P062 Offset Reading
Adds the specified value to the level reading, usually to reference the reading to sea level
or another datum level.
The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.
The Offset Reading is ignored when open channel monitoring (OCM, P600 = 1) is used.
Example
To reference the displayed level to sea level, enter the distance in Units (P005), between
Empty (P006) and sea level. (Enter a negative value if Empty is below sea level.)
Values
Range: -999 to 9999
Preset: 0.000
P006
P007
P062