7ML19981CJ02
MiniRanger Plus – INSTRUCTION MANUAL
Page 53
P200 mA Range
Enables the mA output function by selecting the range and relationship to span. Refer to
mA output on page 40.
P300 Temperature, Transducer Max
The maximum temperature encountered by the integral (transducer) temperature sensor.
P341 Run Time
View the accumulated number of days the MiniRanger Plus has been operating.
P600 Primary Measuring Device
The type of primary measuring device (PMD) used for Open Channel Monitoring (OCM).
P600 must be set to "1" for Flow function which allows access to flow parameters. After
performing a Master Reset (P999), P600 defaults to ’0’ (no OCM calculation).
P604 Maximum Flow
The maximum flowrate associated with the top of Span (P007).
This value represents the flow at the highest head level supported by the PMD. It works
in conjunction with Span (P007) to define the highest point in the curve.
Use this parameter with Time Units (P606) to define the flowrate units.
Values
1
0 to 20 mA
2
4 to 20 mA
3
20 to 0 mA
4
20 to 4 mA
Note:
OCM calculation is an optional feature. MiniRangers with the OCM feature
have this icon on the front:
.
Values
0
off (no OCM calculation, default)
1
Universal Linear Flow Calculation (see P610, P611)
Note:
When P600=1, then P112 Relay A Setpoint and P113 Relay B Setpoint are
not applicable.
Values
Range: 0 to 30,000
Preset: 100