Complete Parts List available at www.MillerWelds.com
OM-258900 Page 22
!
Always ground generator frame to
vehicle frame to prevent electric
shock and static electricity hazards.
!
Also see AWS Safety & Health Fact
Sheet No. 29, Grounding of Portable
And Vehicle Mounted Welding Gen-
erators.
!
Bed liners, shipping skids, and
some running gear insulate the
welder/generator from the vehicle
frame. Always connect a ground
wire from the generator equipment
grounding terminal to bare metal on
the vehicle frame as shown.
!
Use GFCI protection when operat-
ing auxiliary equipment. If unit does
not have GFCI receptacles, use
GFCI-protected extension cord. Do
not use GFCI receptacles to power
life support equipment.
1
Equipment Grounding Terminal (On
Front Panel)
2
Grounding Cable (Not Supplied)
3
Metal Vehicle Frame
Connect cable from equipment ground
terminal to metal vehicle frame. Use #8
AWG or larger insulated copper wire.
Electrically bond generator frame to
vehicle frame by metal-to-metal con-
tact.
5-2. Grounding Generator To Truck Or Trailer Frame
rot_grnd2 2012
−
03
−
800 652-D
1
3
2
GND/PE
5-3. Installing Exhaust Pipe
259 703
!
Stop engine and let cool.
!
Do not blow exhaust toward
right side of unit where air inlet
is or air cleaner may need to be
replaced more often. Point ex-
haust pipe in desired direction
but always away from front
panel and direction of travel.
1
Exhaust Pipe
2
Exhaust Pipe Clamp
Slide clamp over muffler pipe. Slide
exhaust pipe onto muffler pipe and ro-
tate exhaust pipe to desired position.
Secure exhaust pipe with clamp.
Tools Needed:
9/16 in. Or 14 mm
1
2
Summary of Contents for Trailblazer 325 Diesel
Page 18: ...OM 258900 Page 14...
Page 33: ...Complete Parts List available at www MillerWelds com OM 258900 Page 29 Notes...
Page 47: ...Complete Parts List available at www MillerWelds com OM 258900 Page 43 259 872 258 899 C...
Page 53: ...Complete Parts List available at www MillerWelds com OM 258900 Page 49 Notes...
Page 55: ...OM 258900 Page 51 258849 E...