OM-258900 Page 54
11-5. Approximate Power Requirements For Industrial Motors
Industrial Motors
Rating
Starting Watts
Running Watts
Split Phase
1/8 HP
800
300
1/6 HP
1225
500
1/4 HP
1600
600
1/3 HP
2100
700
1/2 HP
3175
875
Capacitor Start-Induction Run
1/3 HP
2020
720
1/2 HP
3075
975
3/4 HP
4500
1400
1 HP
6100
1600
1-1/2 HP
8200
2200
2 HP
10,550
2850
3 HP
15,900
3900
5 HP
23,300
6800
Capacitor Start-Capacitor Run
1-1/2 HP
8100
2000
5 HP
23,300
6000
7-1/2 HP
35,000
8000
10 HP
46,700
10,700
Fan Duty
1/8 HP
1000
400
1/6 HP
1400
550
1/4 HP
1850
650
1/3 HP
2400
800
1/2 HP
3500
1100
11-6. Approximate Power Requirements For Farm/Home Equipment
Farm/Home Equipment
Rating
Starting Watts
Running Watts
Stock Tank De-Icer
1000
1000
Grain Cleaner
1/4 HP
1650
650
Portable Conveyor
1/2 HP
3400
1000
Grain Elevator
3/4 HP
4400
1400
Milk Cooler
2900
1100
Milker (Vacuum Pump)
2 HP
10,500
2800
Farm Duty Motors Std. (e.g. Conveyors, Feed
Augers, Air Compressors)
1/3 HP
1720
720
1/2 HP
2575
975
3/4 HP
4500
1400
1 HP
6100
1600
1-1/2 HP
8200
2200
2 HP
10,550
2850
3 HP
15,900
3900
5 HP
23,300
6800
Farm Duty Motors High Torque
(e.g. Barn Cleaners, Silo Unloaders, Silo Hoists,
Bunk Feeders)
1-1/2 HP
8100
2000
5 HP
23,300
6000
7-1/2 HP
35,000
8000
10 HP
46,700
10,700
3-1/2 cu. ft. Mixer
1/2 HP
3300
1000
High Pressure 1.8 Gal/Min
500 PSI
3150
950
Washer 2 gal/min
550 PSI
4500
1400
700 PSI
6100
1600
Refrigerator or Freezer
3100
800
Shallow Well Pump
1/3 HP
2150
750
1/2 HP
3100
1000
Sump Pump
1/3 HP
2100
800
1/2 HP
3200
1050
Summary of Contents for Trailblazer 325 Diesel
Page 18: ...OM 258900 Page 14...
Page 33: ...Complete Parts List available at www MillerWelds com OM 258900 Page 29 Notes...
Page 47: ...Complete Parts List available at www MillerWelds com OM 258900 Page 43 259 872 258 899 C...
Page 53: ...Complete Parts List available at www MillerWelds com OM 258900 Page 49 Notes...
Page 55: ...OM 258900 Page 51 258849 E...