OM-231185 Page 20
5-9. Electrical Service Guide
Elec Serv 2014
−
01
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
NOTICE
−
INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of
input power at rated frequency
(+
10%) and voltage
(+
10%). Phase to ground voltage shall not 10% of rated input voltage. Do not use a genera-
tor with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
.
Actual input voltage should not exceed
±
10% of indicated required input voltage. If actual input voltage is outside of this range, output may not
be available.
50/60 Hz
Three
Phase
Input Voltage (V)
400
Input Amperes (A) At Rated Output
10.4
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
10
Normal Operating Fuses
3
15
Min Input Conductor Size In AWG (mm
2
)
4
14
(2)
Max Recommended Input Conductor Length In Meters (Feet)
68
(223)
Min Grounding Conductor Size In AWG (mm
2
)
4
14
(2)
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Notes
Summary of Contents for Auto-Axcess 300 CE
Page 27: ...OM 231185 Page 21 Notes...
Page 58: ...OM 231185 Page 52 Figure 10 2 Circuit Diagram For Welding Power Source Part 2 Of 2...
Page 59: ...OM 231185 Page 53 263 490 B Part 2 Of 2 RC1 PLG...
Page 60: ...OM 231185 Page 54 Figure 10 3 Circuit Diagram For 72 Pin Robot Interface...
Page 61: ...OM 231185 Page 55 219 266 D...
Page 62: ...OM 231185 Page 56 Figure 10 4 Circuit Diagram For Peripheral Motor Interface...
Page 63: ...OM 231185 Page 57 219 267 B...
Page 72: ...Notes...
Page 73: ...Notes...
Page 74: ...Notes...