background image

   

   

   Table 2: FUNCTION Codes

3. PUSH-BUTTONS OPERATION

a) Trip test

       

b) Trip reset

    

c) View setting
   

f) Program setting

      Only function codes from 4 to 8 can be programmed.

 

   

Step 1: 

   
   Step 2:

   

Step 3:

   

   

Step 4:

4. OUTPUT CONTACTS

Press  RESET  key  until  the  function  digit 

shows required function.

Press  the  UP  and  DOWN  key 

simultaneously  to  enter  programming 

mode.  The  function  digit  will    blink  to 

indicate  the  relay  is  in  programming 
Use  the  UP  or  DOWN  key  to  select  the 

desired value. 
To  save  the  selected  value, press  the 

UP and DOWN key simultaneously again. 

It will exit the programming mode with the 

data digits displaying new setting.

To  exit  programming  mode  without  saving  the 

selected setting, press the RESET key once.

Figure 1: Scroll sequence

 

When  the  relay  is  not  under  tripped  condition, 

pressing the  “RESET”  key  will  scroll through  the 

various functions.

 

5. SOFT SWITCHES

 

The NX231A incorporates 4 soft switches for system 

configuration. When the function digit shows “8”, the 

relay is in soft switch setting mode. 

 

 Table 3: Soft switch setting

 

SW

1

3

SVL

00
01

00
01

System configuration

High-set disabled.
High-set enabled.

“   ”

switch number (SW)

switch value (SVL)

2

00
01
10
11

 

The NX231A has two sets of output contact:

 (i) CONTACT R1  - linked to trip signal.
 

The output  contact  can be programmed to be either 

auto reset type or manual reset type.
For auto reset type, the contact remain activated until 

the fault current is removed.
For manual reset type, the contact remain activated. 

 (i) CONTACT R2  - linked to trip or start signal.

Contact R2 linked to trip signal auto reset type.

Contact R1 linked to trip signal auto reset type.
Contact R1 linked to trip signal manual reset type.

Contact R2 linked to trip signal manual reset type.
Contact R2 linked to start signal auto reset type.

Contact R2 linked to start signal manual reset type.

    

7. CONNECTION DIAGRAMS

     Earth Fault Relay

  

  

Indicators

    

Mechanical

    

  

 

 

Outputs

  

 

 Setting Ranges

    Low-set setting I>.....................0.10 - 5.00 A (2%-100%)

    High-set setting I>> .................0.10 - 50.0 A (2%-1000%)

    High-set definite time t>>.........0.00 - 100 s

    Low-set definite time t > ..........0.00 - 100 s

6. TECHNICAL DATA

    

    Ratings

    Rated current 

I

n

 ......................5 A

    Frequency ...............................50 Hz or 60 Hz

    Burden ....................................< 0.3 VA at 

I

n

   

    Auxiliary Supply

    

    NX231A-240A.........................198 ~ 265 VAC

    Supply frequency ....................50 Hz or 60 Hz

    VA rating ..................................3 VA typical

    NX231A-110A..........................94 ~ 127 VAC

L1

L2

L3

N

 NX231A

R1

R2

       Auxiliary supply .....................Green LED indicator

       Pick up ..................................Red LED indicator

       Trip ........................................7-segment LED and 

Red LED indicators

Display blinks “T.E.S.T.”, indicators I> and I>> after

test tripped.

Press and hold the “TEST” key for 3.5 seconds to 

stimulate a trip.

Indicator 

FUNCTION 

DP 

DATA 

off 

Earth-fault current 

blink  Last trip elapsed time 

blink  Previous tripped current 

off 

Low-set current setting 

off 

Low-set time delay setting 

off 

High-set current setting 

off 

High-set time delay setting 

off 

Soft switch setting 

 

d) Last Trip Elapsed Time

The function LED shows "t." and time elapsed after 

last trip in day ("d"), hour ("h") and minute ("n"). If 

more than 99 days, the display shows "99d" and 

"oUr"

e) Trip Current Record

By default the most recent ("1") trip current is shown. 

Press "UP" or "DOWN" key to show the previous 

("2") and oldest ("3") trip current.

4

50 Network frequency 50 Hz
60 Network frequency 60 Hz

Thermal withstand.....................4 x In continuous

       Rated voltage ..........................250 VAC
       Continuous carry .....................5A (cos

      

= 1.0)

       Expected electrical life ............10

5

 operations

       Expected mechanical life ........5 x10

6

 operations

Environmental conditions

Temperature ......................... -10ºC to 55ºC

Humidity ............................... 5% to 95% non-condensing

Mounting............................... Panel mounting

Dimension (mm) ................... 96(w) x 96(h) x 110(d)

Enclosure protection............. IP54 at the panel

Approximate weight.............. 0.7 kg

Accuracy

       Protection thresholds ...............± 5%

       Time delay.................................± 5% with a

                                                          mimimum of 50ms

Display off Mode

To toggle display off mode, press “RESET” for 10 

seconds. When display off mode enabled, the 

display will switch off after 6 minutes if no key is 

pressed.

Press the “RESET” key to reset the relay when 

tripped

    (0.00 - 1.00, step 0.01; 1.00-10.0, step 0.10; 10.0-100, step 0.5)