Read Only (Function 0x03 or 0x04)
Register
Description
Type
Min. Unit
Range
4000-
4001
Negative Real Energy
dword
1kWh
0 ~ 1000000M
4002-4003
Positive Real Energy
dword
1kWh
0 ~ 1000000M
4004-4005
Reserved
4006-4007
Apparent Energy
dword
1kVAh
0 ~ 1000000M
4008-4009
Negative Reactive Energy
dword
1kVArh
0 ~ 1000000M
4010-4011
Positive Reactive Energy
dword
1kVArh
0 ~ 1000000M
4012-4013
Total Real Power
int
1W
-2000M ~ 2000M
4014-4015
Total Apparent Power
dword
1VA
0 ~ 2000M
4016-4017
Total Reactive Power
int
1VAR
-2000M ~ 2000M
4018
Total Power Factor
word
0.001
0 ~ 1.000
4019
Frequency
word
0.01Hz
45.00 ~ 65.00
4020-4021
Instantaneous Current L1
dword
0.001A
0 ~ 999.9kA
4022-4023
Instantaneous Current L2
dword
0.001A
0 ~ 999.9kA
4024-4025
Instantaneous Current L3
dword
0.001A
0 ~ 999.9kA
4026-4027
Instantaneous Current Ln
dword
0.001A
0 ~ 999.9kA
4028-4029
Voltage Phase L12
dword
0.1V
0 ~ 999.9kV
4030-4031
Voltage Phase L23
dword
0.1V
0 ~ 999.9kV
4032-4033
Voltage Phase L31
dword
0.1V
0 ~ 999.9kV
4034-4035
Voltage Phase L1
dword
0.1V
0 ~ 999.9kV
4036-4037
Voltage Phase L2
dword
0.1V
0 ~ 999.9kV
4038-4039
Voltage Phase L3
dword
0.1V
0 ~ 999.9kV
4040-4041
Real Power L1
int
1W
-2000M ~ 2000M
4042-4043
Real Power L2
int
1W
-2000M ~ 2000M
4044-4045
Real Power L3
int
1W
-2000M ~ 2000M
4046-4047
Apparent Power L1
dword
1VA
0 ~ 2000M
4048-4049
Apparent Power L2
dword
1VA
0 ~ 2000M
4050-4051
Apparent Power L3
dword
1VA
0 ~ 2000M