a. Scroll until ”DMD“ is displayed using the UP or DOWN button.
b. Press the NEXT button to change interval value. The “PROG” symbol will displayed and “-” symbol next to
“INT” will blink.
c. Use UP or DOWN button to change value and press NEXT button to confirm and change sub-interval setting.
The “-” symbol next to “SUB” will blink. Press UP or DOWN button to change and NEXT button to confirm.
d. To proceed next setting press DOWN button. To exit programming mode, press the PROG button. The user
will be prompted to confirm the saving of settings if change is made. Refer Section 6.16.
a. Scroll in programming mode until ”SYSt sEt“ is displayed using the UP or the DOWN button.
b. Press the NEXT button. The “PROG” symbol will blink. Use the UP or DOWN button to toggle 3-phase 4-wire
“3P4r” or 3-phase 3-wire “3P3r” symbols.
c. Press the NEXT button to confirm new setting.
d. To proceed next setting press DOWN button. To exit programming mode, press the PROG button. The user
will be prompted to confirm the saving of settings if change is made. Refer Section 6.16.
Demand setting default value is 60/4
System setting default value is 3-phase 4-wire