Mighty Therm HH-PH Installation, Operation And Maintenance Instructions Download Page 15

Mighty Therm HH-PH Hydronic Boilers

Page 15

2F-6. Chilled Water Systems

If the boiler is part of a refrigeration system,

include the right valves to isolate the boiler from the
refrigeration system during times when the boiler is
not operating.

When the boiler piping is connected to heating

coils, which are close to refrigerated air circulation,
install flow control valves or other automatic methods
to prevent gravity circulation of the boiler water
during the cooling cycle.

2F-7. System to Boiler Piping

1.

Install gate valves at the inlet and outlet to the
boiler so it can be isolated for service.

2.

Make sure the pressure relief valve (see Figure
26) has its outlet piped to a drain or floor sink.
Pay special attention to relief valve settings in
installations where the boiler is located on the
ground floor of a tall building, or where the
operating temperature of the boiler is above
210°F (99°C). In both cases, the static pressure
of the system is raised. This would bring raw
water into the system. The factory will furnish a
75 psi (516.8 kPa) setting unless a special setting
is ordered.

3.

Install a low water cutoff device if the boiler is
installed above radiation level.

4.

Install manual and/or automatic air venting
devices at high points in the system to get rid
of air.

5.

Install a correctly sized expansion or
compression tank in accordance with the
manufacturer's instructions.

6.

Support the weight of all water and gas piping
with suitable hangers or floor stands.

7.

Check piping diagrams with local applicable
plumbing, heating and building safety codes.

2F-8. Filling the System

1.

Close all air vents and open the makeup water
valve. Let the system fill slowly.

2.

If a makeup water pump is used, adjust the
pressure switch on the pumping system to
maintain at least 12 psi (82.7 kPa) at the highest
point in the heating loop.

3.

If a water pressure regulator is installed on the
makeup water line, adjust the pressure regulator
to provide at least 12 psi (82.7 kPa) at the
highest point in the heating loop.

4.

Open air vents on all radiation units at the high
points in the piping throughout the system,
unless automatic air vents are installed at those
points.

5.

Run the system circulating pump for at least 30
minutes with the boiler shut off.

6.

Recheck all air vents as described in Step 4 above.

7.

With the system full of water and under normal
operating pressure, the air pressure in the expansion
tank should be at least 12 psi (82.7 kPa).

8.

Start up the boiler following the instructions
found on the inside of the boiler.

9.

Operate the whole system, including the pump,
boiler, and radiation units for 1 hour.

10.

Shut down the entire system and vent all
radiation units and high points in the system
piping as described in Step 4 above.

11.

Close the makeup water valve and check the
strainer in the pressure reducing valve for sedi-
ment or debris. Reopen the makeup water valve.

12.

Check the gauge to make sure the water pressure
is right, and check water level in the system. If
the water level indicated above the boiler shows
that water is at the highest point in the circulating
loop, then the system is ready for operation.

13.

Within 3 days of start-up, recheck all air vents
and expansion tank as described in Steps 4 and 8
above.

2F-9. Minimum Boiler Temperature

The boiler inlet water temperature must be

minimum 110°F (43°C) when the system has come up
to normal operating conditions.  Lower temperature
inlet water may allow the production of condensation
on the outside of the copper finned tubes, which can
block the flue gases and/or cause improper
combustion, leading to heat exchanger sooting.

For systems with lower than 110°F (43°C)

temperature, boiler must be protected from low
temperature return water.  There are many methods of
achieving low temperature protection.  Figures 22 and
25 shows an example of such a system.

FLOW
SWITCH

PRESSURE
RELIEF
VALVE

HIGH-LIMIT
DRY WELL

Figure 26. Pressure Relief Valve.

Summary of Contents for HH-PH

Page 1: ...lation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life...

Page 2: ...ble Water Connections 8 2F 2 Freeze Protection 11 2F 3 Pump Requirements 11 2F 4 Variable Water Flow Systems 13 2F 5 System Pressure Requirements 13 2F 6 Chilled Water Systems 15 2F 7 System to Boiler...

Page 3: ...suring the proper performance and application of Laars products SECTION 1 General Information 1A Introduction This manual provides installation and operation instructions for the Model HH and PH Hydro...

Page 4: ...letely before continuing the installation 2B Field Assembly The HH PH boiler is shipped from the factory with the top assembly in the low profile configuration for outdoor installations The HH PH boil...

Page 5: ...hat only the boiler is served by the vent damper device supplied with the boiler Provide at least six inches clearance between the automatic vent damper and combustible construction and be sure to all...

Page 6: ...n carpeting Never store objects on or around the base of the boiler For rooftop installation see Figure 12 through Figure 14 The boiler must be isolated or otherwise protected from any source of corro...

Page 7: ...e venting system must be installed by a qualified installer and in accordance with the latest edition of ANSI Z223 1 In Canada the installation must be in accordance with CAN1 B149 1 or 2 and any loca...

Page 8: ...es dryer and any appliance not connected to the common venting system Turn on any exhaust fans including range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer...

Page 9: ...Clamps Flue Collector Clamp In Out Header Bracket Heat Exchanger Clamp Bracket REAR TILE COVER FLOW SWITCH CONDUIT GAP CLOSURE GROMMET DRAIN VALVE METAL CHANNEL FOR CAPILLARY TUBE TERMINAL STRIP MANU...

Page 10: ...abel the capillary tubes b Loosen the screw on the capillary tube retaining clip then gently pry the clip apart until it comes free from the thermowell see Figure 19 c Pull the sensing bulbs out of th...

Page 11: ...6 17 1 07 1 4 0 4 15 0 94 1 1 0 3 400 31 1 96 5 2 1 6 25 1 58 3 4 1 0 21 1 32 2 3 0 7 18 1 13 1 7 0 5 Water Flow GPM or L s Pressure drop head loss through the boiler expressed in feet or meters of wa...

Page 12: ...LAARS HEATING SYSTEMS Page 12 Figure 21 Piping Multiple Boilers Primary Secondary System Figure 22 Piping Multiple Boilers Low Temperature System...

Page 13: ...ing zone valves zone pumps or 3 way valves This can result in a high temperature rise across the boiler Laars recommends primary secondary pumping for all variable flow systems The boiler pump in a pr...

Page 14: ...LAARS HEATING SYSTEMS Page 14 Figure 24 Hydronic Piping Primary Secondary Reverse Return Figure 25 Hydronic Piping Primary Secondary Reverse Return Low Temperature...

Page 15: ...e regulator is installed on the makeup water line adjust the pressure regulator to provide at least 12 psi 82 7 kPa at the highest point in the heating loop 4 Open air vents on all radiation units at...

Page 16: ...ally need adjustment 11 Before operating the boiler test the complete gas supply system and all connections for leaks using a soap solution Caution Since some leak test solutions including soap and wa...

Page 17: ...Page 17 Figure 28 Typical Example of Wiring Schematic System 1 TYPICAL WIRING DIAGRAM IGNITION SYSTEM NO 1 STANDING PILOT ON OFF OR MECHANICAL MODULATION Example shown HH and PH Hydronic Boilers 175 2...

Page 18: ...gure 29 Typical Example of Wiring Schematic System 12 TYPICAL WIRING DIAGRAM IGNITION SYSTEM NO 12 ELECTRONIC IGNITION ON OFF OR MECHANICAL MODULATION Example shown HH and PH Hydronic Boilers 325 400...

Page 19: ...ANSI Z21 13 Figure 30 Temperature Controls WARNING For your safety when starting the boiler keep your head and face well away from the lower firebox opening to prevent any risk of personal injury Ven...

Page 20: ...ce the damper must be in the open position when the main burners are operating If the boiler will not operate a Turn off all manual gas supply valves b Turn the main electrical switch OFF c Turn the g...

Page 21: ...valve see Figure 32 6 Remove the two screws that fastens the anti rotation bracket on the left side of the gas valve see Figure 32 7 Remove the pilot gas line and thermocouple shield if present from t...

Page 22: ...e wiring diagram found on the inside of the boiler 23 Install the front access door on the boiler 24 Turn all electrical power to the boiler ON SECTION 5 Parts List for HH and PH Boilers 5A General In...

Page 23: ...Rear 10314902 05 40 Insulation Jacket 10458902 05 WATER SYSTEM 41 Bracket Heat Exchanger 10457000 42 Heat Exchanger Tube Assy Copper R0095502 05 Cupronickel R0095602 05 43 Plug 1 4 Inch NPT P0026800 I...

Page 24: ...0 21 E 23 32 28 29 30 31 25 27 24 28 E 64 65 19 55 63 62 41 43 45 43 39 48 47 A 33 34 42 46 52 51 66 39 69 37 38 35 40 36 C 67 F F 18 7 10 11 6 B 9 8 64 REF 68 D 56 61 A 54 58 43 44 57 17 50 53 49 59...

Page 25: ...Mighty Therm HH PH Hydronic Boilers Page 25...

Page 26: ...LAARS HEATING SYSTEMS Page 26...

Page 27: ...Mighty Therm HH PH Hydronic Boilers Page 27...

Page 28: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laa...

Reviews: