Mighty Therm HH-PH Installation, Operation And Maintenance Instructions Download Page 11

Mighty Therm HH-PH Hydronic Boilers

Page 11

21.

Install the sensing bulb(s) into the appropriate
thermowell (keep in mind that the positions of
the inlet and outlet have been reversed. The inlet
is now behind the outlet).

22.

Fasten the capillary tube(s) by squeezing the
retaining clip together, then tighten the screw.

23.

Feed the two brown wires through the top hole
on the left side until the conduit elbow is against
the jacket.

24.

Fasten the conduit by sliding the retaining nut
over the two brown wires (inside the control
compartment) then screwing it down finger-tight
on the conduit elbow.

25.

Straighten the capillary tubing and fasten it to the
side of the boiler under the channel. Use the self-
tapping screws to fasten the channel to the
jacket.

26.

Attach the two brown wires to terminals No. 5
and 6 on the terminal strip. Keep all wiring away
from surfaces that will get hot during boiler
operation.

27.

Replace the gap closures and tighten the screws
securely.

28.

Replace the three grommets and the cap.

29.

Reinstall the drain plug and drain valves.

30.

Slip the flue collector assembly back down
inside the enclosure.

31.

Carefully slip a hand inside to make sure there
are no gaps between the heat exchanger and the
flue collector.

32.

Check to make sure the wiring is not pinched
against sharp edges, or resting on the collector
assembly.

33.

Replace the two flue collector hold down clamps.

34.

Replace the top assembly and fasten it with the
hex-head screws.

35.

Reinstall the vent cap or drafthood if one was
removed.

36.

On indoor installations, plug the draft hood switch
into the receptacle on the left side of the boiler.

Temperature Rise in °F  °C

20°F 11°C

25°F 14°C

30°F 17°C

35°F 19°C

Size

GPM

L/s

H/L*

GPM

L/s

H/L*

GPM

L/s

H/L*

GPM

L/s

H/L*

ft

m

ft

m

ft

m

ft

m

175

14

0.88

1.0 0.3

11

0.69

0.6

0.2

9

0.57

0.5

0.2

8

0.50

0.3

0.1

250

20

1.26

2.1 0.6

16

1.00

1.2

0.4

13

0.82

0.8

0.2

11

0.69

0.6

0.2

325

25

1.58

3.4 1.0

20

1.26

2.1

0.6

17

1.07

1.4

0.4

15

0.94

1.1

0.3

400

31

1.96

5.2 1.6

25

1.58

3.4

1.0

21

1.32

2.3

0.7

18

1.13

1.7

0.5

Water Flow - GPM or L/s
*Pressure drop (head loss) through the boiler, expressed in feet or meters of water (H

2

0).

Table 3. Temperature Rise.

2F-2. Freeze Protection

Proper precautions for freeze protection are

recommended for boiler installations in areas where
the danger of freezing exists.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,
etc., may prevent a boiler from firing. Any time a
boiler is subjected to freezing conditions, and the
boiler is not able to fire, and/or the water is not
able to circulate, there is a risk of freezing in the
boiler or in the pipes in the system. 
When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the boiler, which could
result in leaking or flooding conditions.

Do not use automotive anti-freeze. Maintaining a

mixture of minimum 50% water and maximum 50%
properly inhibited HVAC glycol, which contains an
antifoamant, is the preferred method of freeze
protection for Mighty Therm boilers. Percentage of
glycol used in the Mighty Therm boiler must not
exceed 50%.
 Typically, this mixture will serve as
burst protection for temperatures down to
approximately -35°F (-30°C). To get the desired
temperature rise across the boiler when the is mixture
is used, increase the water flow by 15% above the
original recommendation. Increase the head loss
requirement by 20%

     IMPORTANT NOTES: Different glycol

products may provide varying degrees of protection.
Glycol products must be maintained properly in a
heating system, or they may become ineffective.
Consult the glycol specifications, or the glycol
manufacturer, for information about specific products,
maintenance of solutions, and set up according to your
particular conditions.

2F-3. Pump Requirements

High recovery, low volume water boilers need

enough water flow for efficient operation. The system
pump must develop enough pressure to overcome the
pressure drop of the boiler plus the pressure drop of
the entire circulation system at the flow rates selected
from Table 3.

Summary of Contents for HH-PH

Page 1: ...lation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life...

Page 2: ...ble Water Connections 8 2F 2 Freeze Protection 11 2F 3 Pump Requirements 11 2F 4 Variable Water Flow Systems 13 2F 5 System Pressure Requirements 13 2F 6 Chilled Water Systems 15 2F 7 System to Boiler...

Page 3: ...suring the proper performance and application of Laars products SECTION 1 General Information 1A Introduction This manual provides installation and operation instructions for the Model HH and PH Hydro...

Page 4: ...letely before continuing the installation 2B Field Assembly The HH PH boiler is shipped from the factory with the top assembly in the low profile configuration for outdoor installations The HH PH boil...

Page 5: ...hat only the boiler is served by the vent damper device supplied with the boiler Provide at least six inches clearance between the automatic vent damper and combustible construction and be sure to all...

Page 6: ...n carpeting Never store objects on or around the base of the boiler For rooftop installation see Figure 12 through Figure 14 The boiler must be isolated or otherwise protected from any source of corro...

Page 7: ...e venting system must be installed by a qualified installer and in accordance with the latest edition of ANSI Z223 1 In Canada the installation must be in accordance with CAN1 B149 1 or 2 and any loca...

Page 8: ...es dryer and any appliance not connected to the common venting system Turn on any exhaust fans including range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer...

Page 9: ...Clamps Flue Collector Clamp In Out Header Bracket Heat Exchanger Clamp Bracket REAR TILE COVER FLOW SWITCH CONDUIT GAP CLOSURE GROMMET DRAIN VALVE METAL CHANNEL FOR CAPILLARY TUBE TERMINAL STRIP MANU...

Page 10: ...abel the capillary tubes b Loosen the screw on the capillary tube retaining clip then gently pry the clip apart until it comes free from the thermowell see Figure 19 c Pull the sensing bulbs out of th...

Page 11: ...6 17 1 07 1 4 0 4 15 0 94 1 1 0 3 400 31 1 96 5 2 1 6 25 1 58 3 4 1 0 21 1 32 2 3 0 7 18 1 13 1 7 0 5 Water Flow GPM or L s Pressure drop head loss through the boiler expressed in feet or meters of wa...

Page 12: ...LAARS HEATING SYSTEMS Page 12 Figure 21 Piping Multiple Boilers Primary Secondary System Figure 22 Piping Multiple Boilers Low Temperature System...

Page 13: ...ing zone valves zone pumps or 3 way valves This can result in a high temperature rise across the boiler Laars recommends primary secondary pumping for all variable flow systems The boiler pump in a pr...

Page 14: ...LAARS HEATING SYSTEMS Page 14 Figure 24 Hydronic Piping Primary Secondary Reverse Return Figure 25 Hydronic Piping Primary Secondary Reverse Return Low Temperature...

Page 15: ...e regulator is installed on the makeup water line adjust the pressure regulator to provide at least 12 psi 82 7 kPa at the highest point in the heating loop 4 Open air vents on all radiation units at...

Page 16: ...ally need adjustment 11 Before operating the boiler test the complete gas supply system and all connections for leaks using a soap solution Caution Since some leak test solutions including soap and wa...

Page 17: ...Page 17 Figure 28 Typical Example of Wiring Schematic System 1 TYPICAL WIRING DIAGRAM IGNITION SYSTEM NO 1 STANDING PILOT ON OFF OR MECHANICAL MODULATION Example shown HH and PH Hydronic Boilers 175 2...

Page 18: ...gure 29 Typical Example of Wiring Schematic System 12 TYPICAL WIRING DIAGRAM IGNITION SYSTEM NO 12 ELECTRONIC IGNITION ON OFF OR MECHANICAL MODULATION Example shown HH and PH Hydronic Boilers 325 400...

Page 19: ...ANSI Z21 13 Figure 30 Temperature Controls WARNING For your safety when starting the boiler keep your head and face well away from the lower firebox opening to prevent any risk of personal injury Ven...

Page 20: ...ce the damper must be in the open position when the main burners are operating If the boiler will not operate a Turn off all manual gas supply valves b Turn the main electrical switch OFF c Turn the g...

Page 21: ...valve see Figure 32 6 Remove the two screws that fastens the anti rotation bracket on the left side of the gas valve see Figure 32 7 Remove the pilot gas line and thermocouple shield if present from t...

Page 22: ...e wiring diagram found on the inside of the boiler 23 Install the front access door on the boiler 24 Turn all electrical power to the boiler ON SECTION 5 Parts List for HH and PH Boilers 5A General In...

Page 23: ...Rear 10314902 05 40 Insulation Jacket 10458902 05 WATER SYSTEM 41 Bracket Heat Exchanger 10457000 42 Heat Exchanger Tube Assy Copper R0095502 05 Cupronickel R0095602 05 43 Plug 1 4 Inch NPT P0026800 I...

Page 24: ...0 21 E 23 32 28 29 30 31 25 27 24 28 E 64 65 19 55 63 62 41 43 45 43 39 48 47 A 33 34 42 46 52 51 66 39 69 37 38 35 40 36 C 67 F F 18 7 10 11 6 B 9 8 64 REF 68 D 56 61 A 54 58 43 44 57 17 50 53 49 59...

Page 25: ...Mighty Therm HH PH Hydronic Boilers Page 25...

Page 26: ...LAARS HEATING SYSTEMS Page 26...

Page 27: ...Mighty Therm HH PH Hydronic Boilers Page 27...

Page 28: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laa...

Reviews: