Keep in mind, depending on the model you purchase, some ACE or ACHT units have less or more cubic volume inside.

Units with th

2000

 BTU A

/C Unit, and units with the 

500

 Watt Heater (aka: T-20s) - with an internal heat load of 

200

 watts: 

Mier’s “

• 

ACHT

” and “

ACE

” models which come with a 2000 BTU A/C Unit, when installed and functioning properly, will maintain an internal 

preset temperature of (+/- 3

0

 F).  For example the BW-124ACE (enclosure size 24”W x 24”H x 12”D) is capable of  maintaining an 80

0

 F internal 

temperature (+/- 3

0

 F) up to an outside temperature of 135

0

F.

Mier’s “

• 

ACHT

” models which come with a 500W Heater integrated into the A/C unit, when installed and functioning properly, will maintain an 

internal temperature (+/- 3

0

 F).  For example the BW-124ACHT (enclosure size 24”x24”x12”) maintains a preset temperature (+/- 3

0

 F) up to a 

maximum of up to 60

0

 F with an outside temperature of -20

0

 F.  The BW-136ACHT (enclosure size 24”x36”x12”) maintains a preset temperature 

(+/- 3

0

 F) up to a maximum of up to 60

0

 F with an outside temperature of -10

0

 F. 

Units with t

he 

800

 BTU A/C U

nit, and units with the 

150

 Watt Heater (aka: T-15s) - with an internal heat load of 

100

 watts: 

Mier’s “

• 

8ACHT

” and “

8ACE

” models which come with the smaller 800 BTU A/C Unit, when installed and functioning properly, will maintain 

an internal preset temperature (+/- 3

0

 F).  For example the BW-1248ACE (enclosure size 24”x24”x8”) is capable of maintaining an 80

0

 F internal 

temperature (+/- 3

0

 F) up to an outside temperature of 125

0

F.  

Mier’s “

• 

8ACHT

” models which come with a 150W Heater integrated into the A/C unit, when installed and functioning properly, will maintain an 

internal temperature (+/- 3

0

 F).  For example the BW-1248ACHT (enclosure size 24”x24”x8”) maintains a preset temperature (+/- 3

0

 F) 40

0

 F inter-

nal temperature down to an outside temperature of -20

0

F.

Mier’s Temperature Controlled Enclosures are completely sealed with no knockouts or holes in the enclosure other than those for 

mounting the AC unit.  When installed correctly with the AC unit

 

they meet NEMA 4 standards and may be used either indoors or outdoors, 

and provide a degree of protection to personnel against incidental contact with the enclosed equipment, and they provide a degree of protection for 

the equipment within from windblown dust, splashing water, hose-directed water, rain, sleet, snow, ice, & dirt.

• This enclosure is properly installed when the top & bottom mounting ears are flush against the wall or mounting struts, and held securely with       

   appropriate bolts, and the hinges face to the 

left

 after the enclosure has been mounted

• Watertight fittings must be used on all openings created by the installer.  The door-gasket provided around the opening of the enclosure must remain 

   in place and never be removed.

• The AC/Heater unit must be mounted with the provided gaskets installed between the AC/Heater unit and the enclosure, using the appropriate pre-

   cut holes on the enclosure, and strictly following the unit’s OEM installation guidelines.  Once attached, these AC/Heater gaskets must also remain in 

   place and never be removed

• The tamper switch should be mounted on the studs at the top of the enclosure

 If you have ANY questions regarding the installation of these products, call Mier Products at 1-800-473-0213

Mier Products’ Temperature Controlled Enclosures

Installation and Warranty Information

Power:

Once installed correctly, the power cords for the AC unit and the heater are within the enclosure.  Thus, the installer/electrician is responsible for get-

ting power inside the enclosure.  

It is up to the installer to cut, 

and properly install with water-tight fittings

, any holes needed to run power within or 

run cables out of these enclosures.  

Both the AC unit and the heater get their 

power

 from 

AC 115V, 60hz

.  Mier recommends the installer/electrician run power into the box 

via flexible or 

rigid conduit, with water-tight fittings, to outlet boxes mounted within the enclosure

.  

Wiring:

 use #12 AWG  standard house wiring to a quad outlet box

Connection:

 

the AC/Heater unit has a standard 3-prong NEMA 5-15P plug and the tamper switch connects to the standard low-voltage alarm circuit.

URGENT!

The AC UNIT which

accompanies this enclosure 

MUST BE KEPT IN THE 

UPRIGHT POSITION 

AT ALL TIMES,

and handled with the utmost care 

during shipping, storage, installation.  

The AC UNIT must be mounted to the 

enclosure using the pre-cut holes and 

supplied gaskets.  

The AC UNIT must be 

installed in the upright position, and 

following OEM instructions in order to 

maintain NEMA rating.

ATTENTION:

WATERTIGHT FITTINGS MUST

BE USED ON ALL OPENINGS!

When installed properly per OEM’s specs:

* AC Unit is UL/cUL 50 Type 3R, 4, 12, 

CE UL file SA6453

* Enclosure meets NEMA 4 Standards 

* Paint meets NEMA 4, UL-1332

* Gasket meets NEMA 4, UL-50, 

UL-844, & FMVSS302 

Flammability & Code Compliance

* Tamper Switch is UL Pending

DO NOT MOUNT

 enclosures equipped with air-conditioners on walls of apartments, offices, condos or homes.  Typical A/C vibration can 

   become a nuisance to those who live/work on the other side of the wall.

* If your installation is in warmer or cooler exterior environments, of if your internal heat load is greater, or if you are installing in a coastal or 

   highly corrosive area call Mier Products for advice on special order units

* Mier recommends only installing units with window in shaded areas; as interior temps of these units reach 20

0

 higher in direct sunlight than units 

   without windows

* Remember to schedule maintenance of 

Air-Filters which MUST BE CLEANED PERIODICALLY

*  The unit with the 

MOST COOLING AND HEATING PER CUBIC INCH

, and most highly recommended, is the 

“BW-124ACHT”

Form# MP0100802-3/16

For ON-SITE inspection & repair of A/C units, or A/C Tech Support, call McLean Customer Service at 763-422-2277

In the case of Temperature Controlled Enclosures, units needing repair are repaired onsite and should not be removed.  In the rare case these units 

would be returned, the returnee 

must first obtain an RMA#, follow the strict shipping and packaging guidelines

.  The enclosures and AC Units must be 

shipped on their own skid, and within the original packaging.  REMEMBER: The AC Unit must be kept upright at all times. 

800-473-0213  |  [email protected]  |  www.mierproducts.com

Summary of Contents for ACHT Series

Page 1: ...k you would need at least a NEMA 4 or NEMA 4X unit Mier commonly recommends the highest NEMA rated and most effective Temperature Controlled units which are the ACHT series enclosures NOTE To keep NEMA Rating installers must strictly follow OEM installation instructions and must use water tight fittings on all openings BW 124 8 ACHT 24 W x 24 H x 8 D with an 800 BTU AC unit and 150W heater BW 136A...

Page 2: ...ust also remain in place and never be removed The tamper switch should be mounted on the studs at the top of the enclosure If you have ANY questions regarding the installation of these products call Mier Products at 1 800 473 0213 Mier Products Temperature Controlled Enclosures Installation and Warranty Information Power Once installed correctly the power cords for the AC unit and the heater are w...

Page 3: ...ures and preforming steps 1 2 PRIOR to going to job site 1 Attach the two 2 rails to the enclosure by placing them flat against the Mounting Brackets on top and bottom of the enclosure corresponding to the mounting holes Then place the 3 8 x 16 Bolts through the Rails and the holes in the enclosure Mounting Brackets Secure with the 3 8 Washers on the outside and 3 8 x 16 Flange Nuts on the inside ...

Page 4: ...s through the Mounting Rails and Adjustable Band Guides and secure with the 1 4 x 20 locknuts on the inside C and B 4 Insert the two 2 Heavy Duty Adjustable Bands into the two 2 Adjustable Band Guides inside the Mounting Rails The bands should curve outwards away from the inside of the Mounting Rails One 1 of these Heavy Duty Adjustable Bands goes in each of the Adjustable Band Guides assembled in...

Page 5: ...tches and one Tubular Lock with a set of two keys Dimensions and Weight Outside dimensions without AC attached 24 8 W x 38 5 H x 12 8 D Outside dimensions with AC unit attached are 32 75 W x 38 5 H x 12 8 D Inside dimensions are 23 9 W x 35 9 H x 11 9 D Internal back panel dimensions 22 x34 Enclosure with back panel weighs 70 lbs AC unit weighs 60 lbs Shipping skid weighs 45 lbs External 0 580 mou...

Reviews: