1
General Control Scheme Flowchart
Sections 3-2 to 3-8 on the following pages detail when each of the controls in the flowchart below is activated.
Legend
Numbers in the top right-hand corners
of boxes indicate the relevant section
of text on the following pages.
Conditions met
for oil return
Conditions met
for defrosting
Thermo on
Special control
Outdoor unit duty cycling
Oil return operation
Defrosting operation
7
Stop operation
Abnormal shutdown
System stops
A unit stops when the load demanded decreases
2
Standby control
Crankcase heater control
3
Startup control
Compressor startup delay control
Startup control for cooling only/main cooling
operation
Startup control for heating only/main heating
operation
4
Thermo on
Normal operation control
Component control during normal operation
Compressor control
Heat exchanger control
Electronic expansion valve control
Outdoor fan control
5
Protection control
High pressure protection control
Low pressure protection control
Discharge temperature protection control
Over-current protection control
Ambient temperature out of range protection
control
Inverter module temperature protection control
Wet compression protection control
High pressure ratio protection control
6
Other control
Overload control
Pump-down control
Snow-blowing control
Auto mode and Dual set
points
Low noise mode
Power limitation mode
8