V6R VRF 50Hz
50
Midea V
6
R
Series S
er
vice M
anual
8.5
Low Noise Mode
Low noise mode is used to decrease the noise produced by outdoor units. There are 3 kinds of low noise mode: night silent
mode, silent mode and super silent mode. When low noise mode activating, both the fan step and compressor are limited.
In order to maintain the reliability of V6R system, the lowest fan step for inverter module temperature protection is prior to
low noise control.
Table 3-8.4: Low noise mode
ODU
Night silent mode
Silent mode
Super silent mode
Max. Fan step
Max. frequency step
Max. Fan step
Max. frequency step Max. Fan step
Max. frequency step
8HP
22
Cooling mode 59
Heating mode 68
22
Cooling mode 59
Heating mode 68
19
Cooling mode 52
Heating mode 52
10HP
23
Cooling mode 67
Heating mode 78
23
Cooling mode 67
Heating mode 78
20
Cooling mode 56
Heating mode 56
12HP
24
Cooling mode 72
Heating mode 80
24
Cooling mode 72
Heating mode 80
21
Cooling mode 64
Heating mode 72
14HP
22
Cooling mode 90
Heating mode 106
22
Cooling mode 90
Heating mode 106
19
Cooling mode 77
Heating mode 86
16HP
23
Cooling mode 90
Heating mode 118
23
Cooling mode 90
Heating mode 118
20
Cooling mode 79
Heating mode 106
18HP
24
Cooling mode 102
Heating mode 120
24
Cooling mode 102
Heating mode 120
21
Cooling mode 90
Heating mode 109
8.6
Power Limitation Mode
The energy saving mode is used to limit the system power. It can be used to limit the line selection current or to reduce the
peak current.
Table 3-8.5: Power limitation mode
Power limitation mode setting
Power limitation mode level
Correction factor
n41
Level 1 (Default)
100%
n42
Level 2
90%
n43
Level 3
80%
n44
Level 4
70%
n45
Level 5
60%
n46
Level 6
50%
n47
Level 7
40%