P4, H6: Discharge temperature protection or discharge temperature switch protection
Digital display output
Description
Discharge temperature protection.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Discharge temperature protection
Trigger condition:
For P4 protection: Discharge temperature (T7C1) ≥ 115
o
C.
Recover condition: Discharge temperature (T7C1) < 90
o
C.
Reset method:
For P4 protection: Resume automatically.
Discharge Temp. switch protection
Trigger condition: Discharge temperature ≥ 115
o
C.
Recover condition: Discharge temperature < 75
o
C.
Reset method: Resume automatically.
H6 protection
For H6 protection: P4 protection appears three times in 100 minutes.
Reset method:
For P4 protection: Resume automatically.
For H6 protection: Manually restart.
Possible causes
Outdoor unit stop valves are closed.
Temperature sensor/switch not connected
properly or has malfunction.
Insufficient refrigerant.
System blockage.
Indoor load too large.
System
contains
air
or
nitrogen.
Poor condenser heat exchange.
Outdoor main PCB damaged.