Service manual
37
11.7.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
11.8 Defrosting mode (available for heating mode)
11.8.1 Defrosting condition: Defrosting starts when either of the following
①
&
②
:
①
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
②
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan with
the compressor still running. Add up to 90 minutes.
11.8.2 Defrosting time
At condition
①
, If item B is satisfied before item A, it would be regarded as severe frosting and the
defrosting time is 10 minutes. If item B is satisfied after item A, the defrosting time is 7.5minutes.
At condition
②
, the defrosting time is 10 minutes.
After three times continuous 7.5-minute defrost, the fourth defrost time should be 10 minutes.
The circulation is as following:
7.5 minutes
defrost
7.5 minutes
defrost
7.5 minutes
defrost
7.5 minutes
defrost
11.8.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minutes.
B. The compressor current has reached to
I
DEFROST
or above,
I
DEROST
differs in different models.
11.8.4 Defrosting Actions
Summary of Contents for MSE-07CR
Page 1: ...Cover MSE 07CR MSE 07HR MSE 09CR MSE 09HR MSE 12CR MSE 12HR MSE 18CR MSE 18HR...
Page 12: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Page 14: ...Service manual 11...
Page 15: ...Service manual 12 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Page 16: ...Service manual 13 7 2 Wiring diagram MSE 07CR MSE 09CR MSE 12CR...
Page 17: ...Service manual 14 MSE 07HR MSE 09HR MSE 12HR...
Page 25: ...Service manual 22 discharged...