Service manual
33
11. Electronic function
11.1 Proper symbols and their meaning
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
I
RESTORE
: Amp self-protection return value
TH
DEFROST
: High wind, defrosting temperature difference
TM
DEFROST
: Middle wind, defrosting temperature difference
TL
DEFROST
: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
11.2 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
11.3 Protection
11.3.1 3 minutes delay at restart for compressor.
11.3.2 Sensor protection at open circuit and breaking disconnection
11.3.3 Fan Speed is out of control. When Indoor Fan Speed is too high (higher than 2100RPM) or too low
(lower than 300RPM) lasting 50 seconds, the unit stops and LED displays failure information and can’t
returns to normal operation automatically.
11.3.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and
LED displays failure information and can’t returns to normal operation automatically.
11.3.5 The current protection of the compressor
Summary of Contents for MSE-07CR
Page 1: ...Cover MSE 07CR MSE 07HR MSE 09CR MSE 09HR MSE 12CR MSE 12HR MSE 18CR MSE 18HR...
Page 12: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Page 14: ...Service manual 11...
Page 15: ...Service manual 12 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Page 16: ...Service manual 13 7 2 Wiring diagram MSE 07CR MSE 09CR MSE 12CR...
Page 17: ...Service manual 14 MSE 07HR MSE 09HR MSE 12HR...
Page 25: ...Service manual 22 discharged...