Service manual
35
Anti-freezing control to indoor evaporator at cooling mode ( T: evaporator temp. )
11.6 Dehumidifying mode
11.6.1 The 4-way valve is off in dehumidifying mode
11.6.2 Compressor and Indoor Fan actions in dehumidifying mode
Block
Indoor
Fan
Compressor and Outdoor Fan
LOW
ON 6minutes
BREEZE OFF 4minutes
LOW
ON 5minutes
BREEZE OFF 5minutes
LOW
ON 4minutes
BREEZE OFF 6minutes
A
B
C
Repeat on and off cycle.
11.6.3 Low room temperature protection:
When room temperature decreases to below 10
℃
, compressor and outdoor fan will stop(indoor fan is
Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13
℃
.
11.6.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
11.6.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
11.7 Heating mode
11.7.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode or
turned off. 4-way valve doesn't delay in dehumidifying mode.
11.7.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
11.7.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
Summary of Contents for MSE-07CR
Page 1: ...Cover MSE 07CR MSE 07HR MSE 09CR MSE 09HR MSE 12CR MSE 12HR MSE 18CR MSE 18HR...
Page 12: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Page 14: ...Service manual 11...
Page 15: ...Service manual 12 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Page 16: ...Service manual 13 7 2 Wiring diagram MSE 07CR MSE 09CR MSE 12CR...
Page 17: ...Service manual 14 MSE 07HR MSE 09HR MSE 12HR...
Page 25: ...Service manual 22 discharged...