29
When T1-Ts keeps in the same temp. zone for
3 minutes, the compressor will run as the below
rules:
A~E: Increase the frequency to the higher level
until to F8.
F: Keep the current frequency.
G: Decrease the frequency to the lower level
until to F1.
H: Run at F1 for 1h.(if T1-Ts<-2°C(28.4°F), the
compressor will stop)
Meanwhile, the compressor running frequency
is limited by the current.
I3COOL
I2COOL
Off
Decrease
Hold
Resume
I1COOL
I3COOL, I2COOL,I1COOL mean different
running current value.
Off: Compressor stops.
Decrease: Decrease the running frequency to
the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the
compressor frequency will rise to the higher
level.(frequency will increase twice at most)
8.4.2.2 Outdoor fan running rules
T4
28¡ã
C(82.4¡ã
F)
H
M
L
26¡ã
C(78.8¡ã
F)
22¡ã
C(71.6¡ã
F)
20¡ã
C(68.0¡ã
F)
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time
and the speed can be selected as high,
medium, low, auto and silent mode. When the
compressor is running, the indoor fan is
controlled as below:
For MS11M-09HRFN1-MW0W,
MS11M-12HRFN1-MV0W,
MS11M-18HRFN1-MU0W models:
Auto fan running rules:
For MS11M-09HRFN1-MW0W,
MS11M-12HRFN1-MV0W,
MS11M-18HRFN1-MU0W models:
a
b
c
d
6.0¡ã
C(42.8¡ã
F)
T1-Ts
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
5.0¡ã
C(41.0¡ã
F)
4.0¡ã
C(39.2¡ã
F)
2.5¡ã
C(36.5¡ã
F)
1.0¡ã
C(33.8¡ã
F)
Summary of Contents for Mono 3D
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Page 15: ...13 MS11M 24HRDN1 MT0W...
Page 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Page 17: ...15 MOF 18HFN1 MU0W...
Page 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Page 19: ...17 MOF 18HFN1 MU0W...
Page 20: ...18 MOG 24HFN1 MT0W...
Page 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Page 53: ...51 Take the 9k model as example P U P V...
Page 54: ...52 P W N U...
Page 55: ...53 N V N W...