24
7. Operation Characteristics
Temperature
Mode
Cooling operation
Heating operation
Drying operation
Room temperature
≥17
°C
(62
°F
)
≤30
°C
(86
°F
)
>
10
°C
(50
°F
)
Outdoor temperature
0
°C
~
50
°C
(32
°F
~
122
°F
)
-15
°C
~
30
°C
(5
°F
~
86
°F
)
0
°C
~
50
°C
(32
°F
~
122
°F
)
-15
°C
~
50
°C
(5
°F
~
122
°F
)
(For the models with
low temperature cooling system)
ΔT(℉) =
9ΔT(℃)
5
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features may
come into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this
figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to
its maximum angle (vertically to the floor), and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
Summary of Contents for Mono 3D
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MS11M 09HRFN1 MW0W MS11M 12HRFN1 MV0W MS11M 18HRFN1 MU0W...
Page 15: ...13 MS11M 24HRDN1 MT0W...
Page 16: ...14 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Page 17: ...15 MOF 18HFN1 MU0W...
Page 18: ...16 MOG 24HFN1 MT0W MOC 09HFN1 MW0W MOC 12HFN1 MV0W...
Page 19: ...17 MOF 18HFN1 MU0W...
Page 20: ...18 MOG 24HFN1 MT0W...
Page 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited...
Page 53: ...51 Take the 9k model as example P U P V...
Page 54: ...52 P W N U...
Page 55: ...53 N V N W...