Air Source Screw Water Chiller Unit – Installation Operation and Maintenance Manual
21
(4) Requirements for installing indoor units are as follows:
1.
The distance between the power control cabinet and the windbreak must be larger than 1,000 mm.
2.
The distance between the unit and the windbreak on the side of shell-and-tube end caps must be
larger than 3,500 mm.
3.
The distance between the unit and the ceiling must be larger than 2,000 mm.