Install The Panel MCAC-KTSM-2007-2
146 The Installation of MKA
3. Install the Panel
(1) Remove the inlet grid.
Cat ion
Never put the panel face down on floor or against the wall, or on bulgy objects.
Never crash or strike it.
a. Slide two grid switches toward the middle at the same time, and then pull them up. (Refer to chart 9)
b. Draw the grid up to an angle of about 45o, and remove it. (Refer to chart 10)
(2)Remove the installation covers at the four corners.
Wrench off the bolts, loose the rope of the installation covers, and remove them. (Refer to chart 11)
(3) Install the panel
a. Align the swing motor on the panel to the tubing joints of the body properly. (Refer to chart 12)
b. Fix hooks of the panel at swing motor and its opposite sides to the hooks of corresponding water receiver.
(Refer to chart 12) Then hang the other two panel hooks onto corresponding hangers of the body. (Refer to
chart 12)
Cautions
Do not coil the wiring of the swing motor into the seal sponge.
c. Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly.
(Refer to chart 12)
d. Regulate the panel in the direction of the arrow in Chart12 slightly to fit the panel's center to the center of
the ceiling's opening. Guarantee that hooks of four corners are fixed well.
e. Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and
the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling
well. (Refer to chart 13)
Malfunction described in Chart14 can be caused by inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor unit
should be modified again. (Refer to chart 15-left)
You can modify the height of the indoor unit through the openings on the panel's four corners; if the lift of the
indoor unit and the drainpipe is not influenced (refer to chart 15-right).
(4) Hang the air-in grid to the panel, and then connect the lead terminator of the swing motor and that of the
control box with corresponding terminators on the body respectively.
(5) Relocate the air-in grid in the procedure of reversed order.
(6) Relocate the installation cover.
a. Fasten the rope of installation cover on the bolt of the installation cover. (Refer to chart 16-left)
b. Press the installation cover into the panel slightly. (Refer to chart 16-right)