Wring MCAC-KTSM-2007-2
150 The Installation of MKA
5. Wiring
Caution:
1. The air conditioner should use separate power supply with rated voltage; the voltage of power supply
must be within90%~110% of rated value.
2. The wiring work should be done by qualified persons according to circuit drawing.
3. A disconnection device having an air gap contact separation in all active conductors should
incorporated in the fixed wiring according to the National wiring regulation.
4. Be sure to locate the power wiring and the signal wiring well to avoid cross-disturbance and their
contact with connecting pipe or stop valve body.
5. The wiring (5-core shield cable) attached between the signal receiving board and the wire controller
is not more than 2m. Be sure to prolong it with wiring of the same type and proper length if necessary.
Generally, do not twist two wiring together unless the joint is soldered well and covered with insulator
tape.
6. Do not turn on the power until you have checked carefully after wiring.
7. The yellow and green wire can only be used to link to the ground wiring.