MCAC-KTSM-2007-2 Specifications
Four Way Cassette Type 11
Remark
:
1. All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB
℃
/19.5WB
℃
, water inlet Temp. 7
℃
,
water Temp. difference 5
℃
.
3. Heating capacity test condition:
Air inlet Temp. 21DB
℃
, water inlet Temp. 60 DB
℃
The volume of air and water is same as cooling.
4. Noise level is tested in full-anechoic room.
TYPE
MKA-1500
MKA-1200
Airflow
CFM
1500
1200
m
3
/h
2500
2000
Cooling Capacity
W
11556
9849
Btu/h
39240
33440
Heating Capacity
W
14920
13745
Btu/h
51000
46810
Noise
dB(A)
45
45
Water flow
LPH
2388
1928
Water resistance
kPa
46
44
Indoor
Coil
Number of rows
2
Tube pitch(a)x row pitch(b)
mm
25.4×22
Fin spacing
mm
1.3
Fin type
Hydrophilic aluminum
Tube outside dia.and type
mm
φ7
,
innergroove tube
Coil length x height x width
mm
2000×250×27
Number of circuits
6
Fan
motor
Type
Low noise 3 speed fan motor
Number
1
Model
YDK110-6
Input
W
190
180
Capacitor
uF
5
Indoor
unit
Dimension (W*H*D)
mm
840×310×840
Packing (W*H*D)
mm
1020×410×930
Net/Gross weight
kg
40/50
Panel
Dimension (W*H*D)
mm
950×40×950
Packing (W*H*D)
mm
1030×145×1030
Net/Gross weight
kg
6/11
Control mode
wired controller(optional) ,
remote controller (standard)
Pipe
Water-inlet pipe
RC3/4” internal thread
Water-return pipe
RC3/4” internal thread
Condensation water-outlet pipe
EVA+LDPE 3/4” external thread