Upon completion of wire connection, double check it and then connect the power supply.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a
residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed
wiring according to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
7.2 Specifications of power supply
Medium static pressure duct:
Type
Duct type indoor unit
Outdoor unit
Model
MTA-76C(H)RN1
MTA-150CRN1
MOV-76C(H)N1-C
Power
220-240V~, 1Ph, 50Hz
380~415V~, 3Ph, 50Hz
Switch capacity of the
main power supply / Fuse
20A/8A
20A/12A
60A/40A
Indoor unit power cable
3×2.5mm
2
(Includes grounded wire)
/
Outdoor unit power cable
\
Single unit: 5×6mm
2
Power-main unit: 5×10mm
2
Main-auxil unit: 5×6mm
2
Connective wire of indoor
and outdoor unit
4×1.0mm
2
(Cooling & heating)
2×1.0mm
2
(Cooling only)
Wired controller
connective wire
5×0.5mm
2
(Shield wire)
\
Type
Indoor unit
Outdoor unit
Model
MTA-96C(H)RN1
MOV-96C(H)N1-C
Power
220-240V~, 1Ph, 50Hz
380~415V~, 3Ph, 50Hz
Switch capacity of the main
power supply / Fuse
20A/8A
60A/40A
Indoor unit power cable
3×2.5mm
2
(Includes grounded wire)
/
Outdoor unit power cable
\
5×6.0mm
2
Connective wire of indoor
and outdoor unit
4×1.0mm
2
(Cooling & heating)
2×1.0mm
2
(Cooling only)
Wired controller connective
wire
5×0.5mm
2
(Shield wire)
\