The refrigerant pipe adapter is located inside the outdoor unit. So remove the right front board
first, totally three pieces of M5 screw.
When the pipe is connected from the front side, the pipe can be led out through the right front
board.
When welding the refrigerant pipe, in order to prevent internal oxidation of the pipe, nitrogen
must be filled in. Otherwise, the oxidized chips may block refrigerating circulatory system.
Trash and foreign matters may come into the pipe in the process of installing the refrigerant pipe.
Be sure to blow them off with nitrogen before connecting the pipe to the outdoor units.
Use high-pressure nitrogen to clean the pipelines. Do not use the refrigerant of the outdoor unit
for cleaning.
Pipes size of the units:
Capacity
Liquid pipe
Gas pipe
Set
22 kW
Φ9.52mm
Φ22mm
1
28 kW
Φ9.52mm
Φ25mm
1
35 kW
Φ12.7mm
Φ28.6mm
1
44 kW
Φ9.52mm
Φ22mm
2
For 44kW duct unit, the indoor unit and outdoor unit are categorized in system A and B. When
installing and connecting the indoor unit and outdoor unit, identify the label carefully, and make
sure that indoor unit corresponds to the outdoor unit, exactly. Otherwise, it may lead to fault of
the air conditioner.