-UTSM-12
84
Fig-29
Tighten the nut
Align with the connective pipe
Screw up the connection pipe nut manually, and use a spanner to tighten it as shown in Fig-30
Fig-30
NOTE:
According to the installation conditions, too large torque will damage the flaring, and too small torque will lead to looseness and
leakage. Determine the tightening torque by reference to the following table.
Replenishment quantity of refrigerant required for air conditioner
The single-pass pipe is shorter than 5 m, and no additional length is required (note: The unit has been
replenished before being shipped).
If the single-pass pipe length is 5 m or more, the quantity of fluorine required to be replenished is 0.060X (L-5).
(Unit: kg)
Record the replenishment quantity of the refrigerant and keep the record properly for reference in future
maintenance.
Table 3:
Pipe diameter
Torque
φ
6.35
1420~1720N.cm
(144~176kgf.cm)
φ
9.53
3270~3990N.cm
(333~407kgf.cm)
φ
12.7
4950~6030N.cm
(504~616kgf.cm)
φ
16.0
6180~7540N.cm
(630~770kgf.cm)
φ
19.0
9720~11860N.cm
(990~1210kgf.cm)
Summary of Contents for MDFA-76CRN2
Page 7: ...MCAC UTSM 12 8 3 Dimensions 3 1 MDTA 76C H RN2 MDTA 96C H RN2...
Page 8: ...MCAC UTSM 12 9 3 2 MDTA 120C H RN2...
Page 11: ...MCAC UTSM 12 12 6 Wiring Diagrams 6 1 MDTA 76CRN2 MDTA 96CRN2...
Page 12: ...MCAC UTSM 12 13 6 2 MDTA 76HRN2 MDTA 96HN2 6 3 MDTA 120CRN2...
Page 13: ...MCAC UTSM 12 14 6 4 MDTA 120HRN2...
Page 36: ...MCAC UTSM 12 37 6 Wiring Diagrams 6 1 MDFA 76CRN2 MDFA 96CRN2 CN20 CN20 CN20...
Page 37: ...MCAC UTSM 12 38 6 2 MDFA 76HRN2 MDFA 96HRN2 CN20 CN20 CN20...
Page 51: ...MCAC UTSM 12 53 2 Dimension 2 1 MDOV 76C H CN2 MDOV 96C H CN2...
Page 52: ...MCAC UTSM 12 54 2 2 MDOV 120C H CN2...
Page 55: ...MCAC UTSM 12 57 4 Wiring Diagrams 4 1 MDOV 76C CN2 MDOV 96C CN2 MDOV 120C CN2...
Page 56: ...MCAC UTSM 12 58 4 2 MDOV 76H CN2 MDOV 96H CN2 MDOV 120H CN2...
Page 87: ...UTSM 12 90 Floor standing type cooling and heating type 76 kBtu h 96 kBtu h...