MCAC-UTSM-12
79
After the pipes between the indoor unit and the outdoor unit are
connected, replenish compressed nitrogen to
perform airtight
test.
NOTE:
1.
The airtight test is performed by using the compressed nitrogen
[2.94MPa (30kg/cm
2
G)].
2.
Tighten the spool of the gas valve and liquid valve before
compressing the nitrogen.
3.
Compress the nitrogen at the air vent of the gas valve.
4.
The gas valve and liquid valve are closed in the process of
compressing the nitrogen.
5.
Do not use oxygen, flammable gas or toxic gas in the airtight
test.
3.7
Vacuumize
Use a vacuum pump to make a vacuum. Do not use refrigerant
gas to expel air.
When making the vacuum, start from the air side.
3.8
Open All Valves
3.9 Additional Charge of Refrigerant
According to the diameter and length of the connective liquid side pipe of the outdoor unit and indoor unit,
calculate the refrigerant replenishment quantity. The refrigerant for replenishment is R407C
.
Table 2:
Diameter of liquid line
Quantity of refrigerant replenished for 1m pipe length
Φ
12.7
0.115kg
Φ
16
0.190kg
3.10 Remove Trash and Moist in the Pipe
Trash and foreign matters may come into the pipe in the process of installing the refrigerant pipe. Be sure to
blow them off with nitrogen before connecting the pipe to the outdoor units.
Use high-pressure nitrogen to clean the pipelines. Do not use the refrigerant of the outdoor unit for cleaning.
3.11 Refrigerant Leak Precautions
This air conditioner uses refrigerant R407C. The R407C is safe refrigerant which is harmless and
non-flammable. The room for placing the air conditioner should have a proper space. Even if refrigerant
leakage occurs, the density threshold will not be crossed. Additional measures may also be taken.
1)
Density threshold: Density of the Freon gas that does not harm the human body. Density threshold of
R407C: 0.3 [kg/m3]
Calculate the total quantity of refrigerant to be replenished (A [kg]). Total refrigerant quantity for 10HP =
refrigerant replenishment quantity upon shipment (11[kg]) + additional refrigerant replenishment
corresponding to the pipe length
Calculate out the indoor volume (B [m3]) (according to the minimum volume)
Calculate out the refrigerant density:
2)
Measures against crossing of the refrigerant density threshold
In order to keep the refrigerant density below the threshold value, please install a mechanic ventilation
device. (Perform ventilation often)
In case frequent ventilation is impossible, please install the leakage detection alarm device linked with the
mechanical ventilation device.
3.6 Airtight Test
Summary of Contents for MDFA-76CRN2
Page 7: ...MCAC UTSM 12 8 3 Dimensions 3 1 MDTA 76C H RN2 MDTA 96C H RN2...
Page 8: ...MCAC UTSM 12 9 3 2 MDTA 120C H RN2...
Page 11: ...MCAC UTSM 12 12 6 Wiring Diagrams 6 1 MDTA 76CRN2 MDTA 96CRN2...
Page 12: ...MCAC UTSM 12 13 6 2 MDTA 76HRN2 MDTA 96HN2 6 3 MDTA 120CRN2...
Page 13: ...MCAC UTSM 12 14 6 4 MDTA 120HRN2...
Page 36: ...MCAC UTSM 12 37 6 Wiring Diagrams 6 1 MDFA 76CRN2 MDFA 96CRN2 CN20 CN20 CN20...
Page 37: ...MCAC UTSM 12 38 6 2 MDFA 76HRN2 MDFA 96HRN2 CN20 CN20 CN20...
Page 51: ...MCAC UTSM 12 53 2 Dimension 2 1 MDOV 76C H CN2 MDOV 96C H CN2...
Page 52: ...MCAC UTSM 12 54 2 2 MDOV 120C H CN2...
Page 55: ...MCAC UTSM 12 57 4 Wiring Diagrams 4 1 MDOV 76C CN2 MDOV 96C CN2 MDOV 120C CN2...
Page 56: ...MCAC UTSM 12 58 4 2 MDOV 76H CN2 MDOV 96H CN2 MDOV 120H CN2...
Page 87: ...UTSM 12 90 Floor standing type cooling and heating type 76 kBtu h 96 kBtu h...