MCAC-HTSM-2007-11
Refrigerant charge
Installation
133
4. Refrigerant charge
1). When the length of the one-way pipe is less than 5m, additional refrigerant charge after vacuuming is
unnecessary.
2). When the length of one-way pipe is over 5m, the additional charge quantity is as follows (unit in gram):
Calculation method:
Refrigerant
Liquid diameter
(
mm
)
Unit amount (g/m)
Formula
R410A
Φ
6.35
15
(L-5)
×
15
Remark: 1. The additional refrigerant charge is simply related with the liquid pipe diameter.
2,
In the up formula,
“
L
”
means the length of liquid pipe between each indoor unit and outdoor
unit (unit: m).
Summary of Contents for M2OA-18HRDN1
Page 2: ......
Page 22: ...Wall mounted Type MCAC HTSM 2007 11 20 Indoor Units l Indoor Unit MSCI 12HRIN1...
Page 27: ...MCAC HTSM 2007 11 Wall mounted Type Indoor Units 25 4 Service Space...
Page 50: ...Four way Cassette Type MCAC HTSM 2007 11 48 Indoor Units 4 Service Space unit mm...
Page 59: ...MCAC HTSM 2007 11 Four way Cassette Type Indoor Units 57 10 Accessories...
Page 65: ...MCAC HTSM 2007 11 Duct Type Indoor Units 63 4 Service Space...
Page 94: ...Service Space MCAC HTSM 2007 11 92 Outdoor Units 4 Service Space...
Page 97: ...MCAC HTSM 2007 11 Wiring Diagrams Outdoor Units 95 M4OA 27HRDN1...
Page 101: ...MCAC HTSM 2007 11 Field Wiring Outdoor Units 99 8 Field Wiring...
Page 152: ...Control device MCAC HTSM 2007 11 150 Control System...
Page 153: ...MCAC HTSM 2007 11 Control device Control System 151...
Page 155: ...MCAC HTSM 2007 11 Control device Control System 153...
Page 157: ...MCAC HTSM 2007 11 Control device Control System 155...
Page 158: ...Control device MCAC HTSM 2007 11 156 Control System...