![Midea M2OA-18HRDN1 User Manual Download Page 125](http://html1.mh-extra.com/html/midea/m2oa-18hrdn1/m2oa-18hrdn1_user-manual_1790707125.webp)
MCAC-HTSM-2007-11
Troubleshooting
Outdoor Units
123
Display
(LED flashes for thirteen times)
Malfunction or Protection
P4
Module protection
Yes
Yes
No
Check the connectors CN4, CN1 in outdoor PCBs
Is connection to connector good? Whether the input
voltage range is 220-240V?
Is the wires to compressor right
Unplug the wiring to compressor,
then restart, whether display the
“
P4
”
again?
Check compressor
Turn on the unit in cooling or heating in different season, use a
frequency meter to test the frequency in one of the three wires to
compressor, if there is frequency in wires, but compressor do not
run, the compressor is defective.
Between U, V, W three terminals, the resistance is ~1
Ώ
.
Repair connector or
Correct voltage
Change main board
No
Summary of Contents for M2OA-18HRDN1
Page 2: ......
Page 22: ...Wall mounted Type MCAC HTSM 2007 11 20 Indoor Units l Indoor Unit MSCI 12HRIN1...
Page 27: ...MCAC HTSM 2007 11 Wall mounted Type Indoor Units 25 4 Service Space...
Page 50: ...Four way Cassette Type MCAC HTSM 2007 11 48 Indoor Units 4 Service Space unit mm...
Page 59: ...MCAC HTSM 2007 11 Four way Cassette Type Indoor Units 57 10 Accessories...
Page 65: ...MCAC HTSM 2007 11 Duct Type Indoor Units 63 4 Service Space...
Page 94: ...Service Space MCAC HTSM 2007 11 92 Outdoor Units 4 Service Space...
Page 97: ...MCAC HTSM 2007 11 Wiring Diagrams Outdoor Units 95 M4OA 27HRDN1...
Page 101: ...MCAC HTSM 2007 11 Field Wiring Outdoor Units 99 8 Field Wiring...
Page 152: ...Control device MCAC HTSM 2007 11 150 Control System...
Page 153: ...MCAC HTSM 2007 11 Control device Control System 151...
Page 155: ...MCAC HTSM 2007 11 Control device Control System 153...
Page 157: ...MCAC HTSM 2007 11 Control device Control System 155...
Page 158: ...Control device MCAC HTSM 2007 11 156 Control System...