Procedure
4.12.4
H6 / HH
is blowing towards the fan, making
the fan running in the wrong direction
Yes
Change the outdoor unit s installation direction or
build a shelter to protect the fan from strong wind
No
DC fan wire is loosed
1
Yes
Reconnect DC fan wire
No
The fan motor is blocked or has failed
Yes
Remove obstruction or replace the fan motor
No
Replace outdoor unit main PCB
Notes:
1.
Refer to Figures 4-1.1 to 4-1.2 in M thermal Mono Service Manual and to Part 2 Wiring Diagrams . in M thermal Mono Engineering Data Book,
2.
Measure the voltage between the DC fan motor power supply
wires. The normal voltage is 15V when the unit is in standby. If the voltage
is significantly different from 15V, the IPM module on the inverter module is damaged. DC fan connection is CN107/109 on the outdoor unit refrigerant
system main PCB (labeled 23 in Figure 4-2.2).