Incinomite - J121-DS - Installation Manual

917 

III FLAME ON ONLY DURING 6-SECOND TRIAL FOR IGNITION

A. With motor running check burner line voltage terminals for 120V as follows:

1. Between strip terminals 

L1

 and 

L2

 - 120V: voltage OK.

2. Between strip terminals 

L1

 and 

GND.TERM.

 - 120V: ground OK.

3. Between strip terminals 

L2

 and 

GND.TERM

. - no volt age: no back-feed neutral OK.

B. Follow test procedure as specifi ed in Step II G.

1. Connect DC microamp meter in series with sense wire and Electronic Control SENSE terminal. 
With fl ame on, fl ame signal should be steady and at least 2 microamps. Check sense wire for 
continuity Adjust  ignitor  gas  pressure  to  obtain  acceptable  signal  and  note  gas  pressure  and 
signal strength for future reference.

IV. SHORT FLAME

A. Low gas pressure
B. Air shutter open too far
C. Input adjuster not set properly

V. LONG HAZY FLAME

A. High gas pressure
B. Air shutter closed too far
C. Insuffi  cient free air in combustion chamber
D. Dirty blower wheel
E. Input adjuster not set properly

VI. GAS FAILS TO SHUT OFF

A. Defective automatic valve
B. High gas pressure

*Normal low voltage: Motor running - 24V minimum Automatic valve energized - 21V minimum
 

 

  

 

    __________________________________________

Trouble Shooting

Continued

Summary of Contents for J121-DS

Page 1: ...witch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re departmen...

Page 2: ...d air at sea level with zero draft over re De rate burner for altitudes over 2 000 feet by 4 for each 1000 feet of additional elevation 4 100 MBH 100 000 BTU Hr No 1 Waste Primarily dry material such...

Page 3: ...MIDCO Accessory Weatherhood will provide such protection CAUTION If the incinerator is of the down draft design make sure that a direct draft vent opening of approximately 10 square inches has been p...

Page 4: ...en pressure testing the supply piping the burner valve train must be protected If the test pressure is 0 5 PSIG or less closing the Main Manual Shut O Valve will su ce CAUTION If the test pressure is...

Page 5: ...t these gases from reaching an explosive level periodically purge the incineration chamber as described in Step 5 9 Observe the ignitor ame If it is weak screw in the Ignitor regulator adjustment to i...

Page 6: ...Load incinerator and make trial run Con rm that the incineration chamber pressure stays within the range of 0 to minus 0 5 W C 16 WARNING When the incinerator is located inside a building and a draft...

Page 7: ...Midco International Inc 7 8471 15 MADE in the USA Part 1 Installation VII Initial Start Up Adjustment Continued Figure 2B Wiring diagram 6455 58 Figure 3 Control Components SCHEMATIC LEGEND...

Page 8: ...is no debris in the Blast Tube that could short out the Spark or Flame Electrode Clean the Ignitor Gas Ori ce in Tee Ori ce Fitting see Figure 5 and check that the ori ce size is correct per Table 3 C...

Page 9: ...nt screw __________________________________________ The valve is a single function on o type with automatic closing on current failure Replace entire valve if valve fails to open when power is applied...

Page 10: ...uring the burner run and not re established within 6 seconds the Control will shut o the Main Automatic Gas Valve and LOCK OUT To reset the Control for restart turn o the Burner Switch or Timer for at...

Page 11: ...trial for ignition 1 Check for 24V between Electronic Control Valve terminal and strip terminal 10 No volt age Electronic Control or Fuse is defective 2 Check for 24V between strip terminals 7 and 10...

Page 12: ...ls L2 and GND TERM no volt age no back feed neutral OK B Follow test procedure as speci ed in Step II G 1 Connect DC microamp meter in series with sense wire and Electronic Control SENSE terminal With...

Reviews: