background image

Midco International Inc. 

3

8471 15

MADE

 in the 

USA

Part 1 Installation

Install the INCINOMITE burner(s) in location(s) specifi ed by the incinerator manufacturer. It should 
be positioned approximately level with the top of the highest normal load and fi re with or across the 
draft fl ow.
- If the incinerator is designed only for No. 4 waste, the level can be lowered to bring the fl ame to play 
directly on the smaller loads characteristic of this type of operation. The opening through which the 
burner fi res should be of a diameter only large enough to accommodate the Blast Tube (4¼″diameter x 
3″ minimum long.) Do not allow the Blast Tube to protrude into the incineration chamber. If necessary, 
build an extension outside of the incinerator wall to increase wall depth.
- To change the Mounting Flange to its alternate position, horizontal or 10° down fi ring, remove the 
four (4) screws that attach it to the burner, rotate the fl ange 180° and reinstall the screws.
-  Before  mounting  the  burner,  check  that  the  Blast Tube  and  Blower  Housing  are  clear  of  foreign 
material and that the Main Gas Port and Nozzle Support is clean and undamaged.
- If the incinerator is located outdoors, the burner and all of its components, except the Main Manual 
Shut-Off  Valve, must be protected from weather. The MIDCO Accessory Weatherhood will provide 
such protection.
 

 

CAUTION: If the incinerator is of the down draft design, make sure that a direct draft 

vent  opening  of  approximately  10  square  inches  has  been  put  through  the  top  of  the  drop 
section(s) to provide for the venting of any gas leakage. See Figure 1.

 
 

  

 

 

 

    __________________________________________

 
The  size  and  type  of  material  used  for  the  vent  connector  and  chimney  must  conform  to  the 
recommendations  of  the  incinerator  manufacturer,  as  well  as  local  and  national  codes.  This  is 
especially true where high fl ue gas temperatures are encountered.
- When natural draft is used and the chimney height is over 25 feet, a barometric damper of the same 
size as the vent connector should be installed. If the chimney is high enough to make it diffi  cult for the 
barometric to maintain a maximum incineration chamber over-fi re draft, 0 to minus 0.5″ W.C., a 

fi xed

 

damper should be installed in the vent connector between the barometric and chimney to restrict the 
chimney draft to a point within the controlling capacity of the barometric. After fi nal setting, the damper 
should  be  permanently  fastened  into  position  per  ANSI  Z223.1-latest  edition  “National  Fuel  Gas 
Code”, or latest edition available from American National Standards Institute to prevent tampering.

 

 

  

 

    __________________________________________

III  Installation

Figure 1

 Typical Installation

IV  Chimney, Vent 
Connector* and Draft 
Control 

*Formerly referred to 
as FLUE PIPE

Summary of Contents for J121-DS

Page 1: ...witch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re departmen...

Page 2: ...d air at sea level with zero draft over re De rate burner for altitudes over 2 000 feet by 4 for each 1000 feet of additional elevation 4 100 MBH 100 000 BTU Hr No 1 Waste Primarily dry material such...

Page 3: ...MIDCO Accessory Weatherhood will provide such protection CAUTION If the incinerator is of the down draft design make sure that a direct draft vent opening of approximately 10 square inches has been p...

Page 4: ...en pressure testing the supply piping the burner valve train must be protected If the test pressure is 0 5 PSIG or less closing the Main Manual Shut O Valve will su ce CAUTION If the test pressure is...

Page 5: ...t these gases from reaching an explosive level periodically purge the incineration chamber as described in Step 5 9 Observe the ignitor ame If it is weak screw in the Ignitor regulator adjustment to i...

Page 6: ...Load incinerator and make trial run Con rm that the incineration chamber pressure stays within the range of 0 to minus 0 5 W C 16 WARNING When the incinerator is located inside a building and a draft...

Page 7: ...Midco International Inc 7 8471 15 MADE in the USA Part 1 Installation VII Initial Start Up Adjustment Continued Figure 2B Wiring diagram 6455 58 Figure 3 Control Components SCHEMATIC LEGEND...

Page 8: ...is no debris in the Blast Tube that could short out the Spark or Flame Electrode Clean the Ignitor Gas Ori ce in Tee Ori ce Fitting see Figure 5 and check that the ori ce size is correct per Table 3 C...

Page 9: ...nt screw __________________________________________ The valve is a single function on o type with automatic closing on current failure Replace entire valve if valve fails to open when power is applied...

Page 10: ...uring the burner run and not re established within 6 seconds the Control will shut o the Main Automatic Gas Valve and LOCK OUT To reset the Control for restart turn o the Burner Switch or Timer for at...

Page 11: ...trial for ignition 1 Check for 24V between Electronic Control Valve terminal and strip terminal 10 No volt age Electronic Control or Fuse is defective 2 Check for 24V between strip terminals 7 and 10...

Page 12: ...ls L2 and GND TERM no volt age no back feed neutral OK B Follow test procedure as speci ed in Step II G 1 Connect DC microamp meter in series with sense wire and Electronic Control SENSE terminal With...

Reviews: