parameter ‘14’ (showing at position of requested water temperature – on the left) with particular
measured value, e.g. ‘30’ (showing at position of current water temperature – on the right). For
example 14 30 would mean that the water temperature on the input to the heat pump (swimming
pool output) is 30°C.
Then repress the „clock“ button to display the parameters in sequence (parameters from 14 to 18).
Note: 10 seconds after the last pressing of the button, the display switches over to the display of the
operational mode.
5.7
Setting of the operating parameters
It is possible to change preset technical parameters of your heat pump. Please be advised that the
manufacturer has fine-tuned the technical parameters in order to achieve the best possible operations
and efficiency. Thus a change in these settings is not advised.
Should there be a need to change manufacturing settings please discuss the matter with your seller or
distributor alternatively with the manufacturer. Change in preset settings may lead into heat pump
undesired performance issues, inefficiency, malfunction, failure or damage. Change can only be
performed by trained technician.
Your heat pump enables settings of 11 operational parameters. Please note that only trained
technician is allowed to perform change in manufacturing preset settings.
In STAND-BY mode (heat pump off) press and hold the „M“ button for 3 seconds. The
parameters will be displayed starting with parameter ‘00’ (showing at position of requested
water temperature – on the left) with particular preset setting, e.g. ‘0’ (showing at position of
current water temperature – on the right).
Then repress the „M“ button to display the parameters in sequence (parameters from 00 to
11, see the chart below).
The requested value is adjusted by pressing the
and
buttons on the particular
parameter.
By keeping the „M“ button pressed for 3 seconds in the operating mode, you can
enter the reading of preset technical parameters, however you cannot change
them. For more information please
see section 5.6 Parameters check.
Figure Meaning
Range
Manufacturing setting
00
Setting of the requested max. water
temperature
0/1
~
45/60°C
0
01
Temperature setting for the beginning
of the defrosting
-20°
~
10°C
-7°C
02
Temperature setting for the end of the
defrosting
5°
~
45°C
13°C
03
Setting of the defrosting time period
30
~
150 min.
45 min.
04
Setting of the forced defrosting time
period
1
~
15 min.
3 min.
05
Setting of the compressor´s
protection temperature
70
~
110°C
95°C
06
Temperature for 4-way valve
activation
0
~
60°C
7°C
07
Working mode of the circulation pump
(0 = Periodical / 1 = Continouos / 2 =
micro)
0
~
2
2*
08
Restart after power cut
0
~
1
(0-no, 1-yes)
1