3. The actual height of capacitance detection ring
is not consistent with its display height
value.
Since "one-keystroke height calibrat
ion" is
so simple and it only needs to press one key,
user may calibrate the height
controller at any time.
6.2 Commissioning procedure of one-key
stroke heig
ht calibration
Check and make sure the
bottom of
capacitance det
ection ring is parallel to the work
piece.
Power on the
height
controller of cutting torch.
Set the detector mode to capacitance detector mode (for the met
hod, see
7.3).
In manual mode, adjust the cutting nozzle to approach
work piece t
o an appropriate
position.
Press and hold t
he "down arrow" key on
the height control panel for about two
seconds, t
he "one-keyst
roke height calibration” process will start a
utomatically as
follo
ws:
1. Move up t
o somewhere about 30mm high in five steps;
2. And t
hen move down to
about 10mm away from t
he work piece and stop;
3. All the calibration is completed.
By this step, the initial commissioning is finished.
For details about how t
o perfo
rm height control operation, see 5.
2 and 5.3.
7 Controller Panel
There are LCD display and keypads on the height controller panel.
Through the panel operations, user can modify relevant parameters and