9 Modbus RTU communication
Modbus RTU register address definition of electromagnetic flowmeter energy meter
Protocol
address
Decimal
(
Decimal
)
9
Protocol
address
Hexadecimal
(
HEX
)
Data Format
Register definition
4112
0x1010
Float Inverse
Instantaneous flow floating point representation
4114
0x1012
Float Inverse
Floating point representation of instantaneous flow rate
(
m/s
)
4116
0x1014
Float Inverse
Reserve
4118
0x1016
Float Inverse
Floating point representation of fluid resistance
4120
0x1018
Long Inverse
Integer part of flow cumulative value
4122
0x101A
Float Inverse
Decimal part of flow cumulative value
4124
0x101C
Unsigned short
Instantaneous cooling capacity unit
0
:
MJ/h; 1
:
GJ/h 2
:
KWh/h; 3: MWh/h
4125
0x101D
Unsigned short
Total refrigeration unit
0
:
MJ
;
1
:
GJ 2
:
KWh
;
3
:
MWh
4126
0x101E
Unsigned short
Instantaneous flow unit
0: l/s
;
1
:
l/m 2
:
l/h
;
3
:
m³/s 4: m³/m
;
5
:
m³/h
4128
0x1020
Unsigned short
Instantaneous heat unit
0
:
MJ/h; 1
:
GJ/h 2
:
KWh/h; 3: MWh/h
4129
0x1021
Unsigned short
Flow cumulative total unit
0: L
;
1: m³
;
2: GAL
;
3: GAL
;
4:kg
;
5:T
;
4130
0x1022
Unsigned short
Pressure range
0
:
0.6MPa1
:
1.6MPa
4131
0x1023
Unsigned short
Total heat unit
0
:
MJ
;
1
:
GJ 2
:
KWh; 3:MWh
4132
0x1024
Unsigned short
Empty Pipe alarm 0
:
Normal
;
1
:
Alarm
4133
0x1025
Unsigned short
System alarm 0
:
Normal
;
1
:
Alarm
4134
0x1026
Float Inverse
Instantaneous heat flow
4136
0x1028
Long Inverse
Total accumulated heat value
4138
0x102A
Float Inverse
Decimal value of total calorie accumulation
4140
0x102C
Unsigned short
Input temperature (
℃
)
4141
0x102D
Unsigned short
output temperature (
℃
)
4142
0x102E
Long Inverse
Total cumulative value of cooling capacity
4144
0x1030
Float Inverse
Total cumulative cooling capacity decimal value
4146
0x1032
Float Inverse Instantaneous cooling capacity
Communication connection RS485 or RS232, Baud rate range 600-9600, communication parameter:
Baud rate, N, 8, 1.
Instrument terminal T+
(
A
)
, T-
(
B
)
and COM.
Communication protocol conforms to MODBUS RTU protocol. In instruction table register number is
register address.
Composition of communication information: Address code - Function code - Data segment - CRC, A
message is sent and received continuously, and the character interval cannot be greater than one
character, otherwise it is regarded as the beginning of a new message or the end of the previous
message. The message body consists of hexadecimal numbers.