background image

21 

range value. 

7.2.3 Pulse output 

There are 16 ways of pulse output of electromagnetic flowmeter heat meter: Flow frequency output, Flow 

pulse Ltr, Flow pulse m

³

,Heat pulse MJ, Heat pulse GJ, Heat pulse KWh, Heat pulse MWh, Cooling 

pulse MWh, Cooling pulse MJ, Cooling pulse GJ, Cooling pulse KWh, Heat and cooling pulse MJ, Heat 

and cooling pulse GJ, Heat and cooling pulse KWh, Heat and cooling output MWh. 

Frequency output method: The frequency output is a continuous square wave, and the frequency value 

corresponds to the flow percentage. 

Pulse output method: The pulse output is a rectangular wave pulse train. Each pulse represents a flow 
equivalent in the pipeline. The pulse equivalent is set by the two parameters of ‘pulse output type’ and 
the following ‘output pulse coefficient’. 
The pulse output mode is mostly used for total accumulation, and is generally connected with an 

accumulating instrument

 

Cooling and heat state output: When the pulse output indicates the cold and hot state, the heat is at low 

level and the cooling capacity is at high level; 

When the pulse output indicates the cold and hot state, the heat is at low level and the cooling capacity is 

at high level; 

When the pulse output indicates the cold and hot state, the heat is low and the cooling capacity is high; 

When the pulse output indicates the cold and hot state, the heat is at low level, and the cold is at high 

level; 

When the pulse output indicates the cold and hot state, the heat is at low level and the cold is at high 

level;   

Flow direction output: When the pulse output indicates the flow direction, the forward direction is low 

level, and the reverse direction is high level. 

7.2.4 Frequency output upper limit 

The electromagnetic flowmeter heat meter frequency corresponds to the percentage output of the flow 

rate

Do not correspond to heat and cold

, Optional range 1~5000. 

Calculated as follows: 

Instrument frequency output value = 

Flow rate measurement value / Flow range

* Frequency full scale 

value; 

7.2.5 Output pulse coefficient 

Impulse coefficient is impulse equivalent, The range is 0.001

59.999, The unit is the same as the unit of 

the selected pulse output type and is used to measure the pulse output. 

7.3 Flow meter location 

If the heat meter flow sensor is insta

lled at the inlet of the heating pipe, please select ‘flow inlet’; if the 

heat meter flow sensor is installed at the outlet of the heating pipe, please select ‘flow outlet’. this 
parameter does not correspond to the actual installation, which will cause calculation errors. 

7.4 Temperature parameter 

7.4.1 Measure water temperature from heat and cooling meters 

The temperature limit for the meter to measure heat and cold. When the temperature is lower than the 

set temperature, the meter does not calculate the heat and cold. 

7.4.2 Working pressure selection 

The electromagnetic heat meter complies with the People's Republic of China's urban construction 

industry standard CJ128-2007. It has two pressures of 0.6MP and 1.6MP, which are convenient for users 

Summary of Contents for MFE600H Series

Page 1: ...MFE600H Operation Manual V2 1...

Page 2: ...f instrument energy meter 19 7 1 Flow parameter 19 7 2 Output parameters 20 7 3 Flow meter location 21 7 4 Temperature parameter 21 7 5 Total amount setting parameters 22 8 Installation requirements 2...

Page 3: ...stitutions 2 Specifications Table 1 Diameter Flange type DN25 DN400 level of accuracy level 2 Electrode type Standard fixed electrode antifouling electrode Structure type Integrated type separated typ...

Page 4: ...ect 220V AC or 24V DC wiring to avoid power wiring faults When wiring select the corresponding power terminal to connect to the power line according to the product specifications and then connect to t...

Page 5: ...according to the required output form See Table 3 for the specific meaning of the integrated electromagnetic flowmeter wiring terminals Table 3 Terminal definition of separated type Terminal Symbol F...

Page 6: ...and a converter and is ready for immediate use when it is supplied All operating data is factory set according to your order please refer to the provided inspection report for details After turning on...

Page 7: ...limit The real time flow value is higher than the set upper limit of alarm value 5 Lower flow limit The real time flow value is lower than the set lower limit of alarm value 5 Operation 5 1 Key instru...

Page 8: ...e done in the secondary menu password modification item Note If you modify level 1 or level 2 password please remember the modified password 6 Parameter setting and method 6 1 Report query In the main...

Page 9: ...tructions Parameter Range 1 Language English 2 Communication address Range 0 255 3 Communication rate Rate 1200 2400 4800 9600 14400 Check no check odd parity Check even parity check 4 Pipe Diameter 3...

Page 10: ...nt Yes No 12 Flow integration unit 1m 0 1m 0 01m 0 001m 1L 0 1L 0 01L 0 001L 1t 0 1t 0 01t 0 001t 1kg 0 1kg 0 01kg 0 001kg 1gal 0 1gal 0 01gal 0 001gal 1ig 0 1ig 0 01ig 0 001ig 13 Pulse output method...

Page 11: ...geable 18 Converter coefficient Factory set unchangeable 19 Converter code value Factory set unchangeable 20 Empty pipe alarm Yes No 21 Empty pipe alarm threshold value Factory set unchangeable Empty...

Page 12: ...Electrode alarm threshold 0 999 9 adjustable 27 Resistance coefficient 28 Current zero point correction Factory set unchangeable 29 Current full scale correction Factory set unchangeable Current Full...

Page 13: ...on linear correction point 2 36 Non linear correction point 3 37 Non linear correction point 4 NonlineCorrenct4 V 1 2000m s K 1 0000 NonlineCorrenct3 V 0 9000m s K 1 0000 NonlineCorrenct2 V 0 6000m s...

Page 14: ...t test 20mA 2000Hz 10mA 1000Hz 4 16mA 20Hz 4mA 1Hz 43 Density of measured fluid As customers request 44 Change rate limit value 0 100 adjustable 45 Insensitive time 0 99S adjustable Slope Limit Time 1...

Page 15: ...ord modification adjustable 50 Date YY MM DD adjustable 51 Time HH MM SS adjustable 52 System running time 53 System time adjustable System Time 2021 03 08 11 57 54 System Run Time 1 Day 13 Hour 34 Mi...

Page 16: ...01GJ 0 1GJ 1GJ 0 0001KWh 0 001KWh 0 01KWh 0 1KWh 1KWh 0 0001MWh 0 001MWh 0 01MWh 0 1MWh 1MWh 60 Cool accumulation unit 0 0001MJ 0 001MJ 0 01MJ 0 1MJ 1MJ 0 0001GJ 0 001GJ 0 01GJ 0 1GJ 1GJ 0 0001KWh 0 0...

Page 17: ...perature difference 67 Cut off the difference between cold and heat Enable Disable 68 Heat meter initial measurement temperature 69 Cold meter initial measurement temperature Cold Start T 0 0000 Heat...

Page 18: ...PT1000 calibration 1 Access standard resistance 1 automatic correction 77 Input PT1000 calibration 2 Access standard resistance 2 automatic correction In Pt1000 Check 2 Input R 1 5k Measure 1498 0 In...

Page 19: ...h MJ h KWh h MWh h 3 Cooling flow unit Choose GJ h MJ h KWh h MWh h 4 Temperature difference signal removal Setting 5 Total heat unit Choose 0 0001MJ 0 001M 0 010MJ 0 100MJ 1 000MJ 0001GJ 0 001GJ 0 0...

Page 20: ...tomatic correction 17 Inlet PT check 2 Access standard resistance 2 Automatic correction 18 Outlet PT check 1 Access standard resistance 1 Automatic correction 19 Outlet PT check 2 Access standard res...

Page 21: ...tings are prohibited 7 2 Output parameters 7 2 1 Current output mode There are six ways of current output of electromagnetic flowmeter energy meter Flow output Heat output Cooling output Cold and heat...

Page 22: ...pulse output indicates the cold and hot state the heat is at low level and the cold is at high level Flow direction output When the pulse output indicates the flow direction the forward direction is...

Page 23: ...l value of the flow which is mainly used for instrument maintenance and instrument replacement The flow cumulative amount can be modified generally cannot exceed the maximum value counted by the count...

Page 24: ...mended When there are valves at the front and rear of the flowmeter the front and rear straight pipe must meet the front 5D and rear 2D installation methods at least and the valve must be fully open a...

Page 25: ...e needed between the flowmeter and the tail end of the elbow as shown in Figure 5 Figure 5 When energy meter is installed at the back end of the expanded diameter pipe the flowmeter and the back end o...

Page 26: ...ference sources as much as possible such as pumps and other equipment to avoid their interference on the measurement as shown in Figure 8 Figure 8 In order to ensure the upstream piping conditions req...

Page 27: ...re range 0 0 6MPa1 1 6MPa 4131 0x1023 Unsigned short Total heat unit 0 MJ 1 GJ 2 KWh 3 MWh 4132 0x1024 Unsigned short Empty Pipe alarm 0 Normal 1 Alarm 4133 0x1025 Unsigned short System alarm 0 Normal...

Page 28: ...en the low byte The high byte is the byte where the sign bit and exponent bit in the floating point number are located and the low byte is the byte where the mantissa is located Above D0 D1 D2 and D3...

Page 29: ...de representation of 2n The bit field length of the mantissa is 23 bits in the figure but it is actually24 bits This bit is invisible and its value is fixed at 1 which means that the effective digits...

Page 30: ...www microsensorcorp com...

Reviews: